Special adjustment for measuring and adjusting CO2 levels
D. Returning to Service:
1.Return slotted cover to original position.
2.Reinstall Torx cover.
3.Remove CO2 analyzer probe and reinstall plug in exhaust collar.
4.Turn ON/OFF switch to the OFF (O) position and then back to the ON (I) position.
5.Heater is ready for normal operation.
|
| Without Front | With Front |
| |
|
| Cover | Cover |
| |
|
| Nat. Gas | Nat. Gas |
| |
max. input | P1 | 9.1 ± 0.1 % | 9.7 ± 0.1 % |
| |
min. input | P2 | 9.4 ± 0.1 % | 9.7 ± 0.1 % |
| |
|
| LP Gas | LP Gas | Fig. 38 | |
max. input | P1 | 10.1 ± 0.1 % | 10.7 ± 0.1 % | ||
| |||||
min. input | P2 | 10.4 ± 0.1 % | 10.7 ± 0.1 % |
| |
* Final reading must be confirmed with the front cover |
| ||||
on, CO2 levels increase when the cover is installed. |
| ||||
Table 7 |
|
|
|
|
Final Readings
P2 CO2 Reading:
P1 CO2 Reading:
%CO2
%CO2
Fig. 37
28 | 6 720 607 440 |