Category | Product ID | Product Description |
| D192G | Bell supervision module |
| D8125 | POPEX module |
| D8125MUX | Zonex to dual multiplex interface |
| D8128D | OctoPOPIT module |
| D8129 | |
| D8130 | Release module |
| D9127U | POPIT module (no tamper) |
| D9127T | POPIT module (tamper) |
| D9131A | Parallel printer interface module |
| DX4020 | Ethernet interface module |
Programming | D5200CE | Handheld programmer |
Products |
|
|
| RPS | Remote Programming Software |
| Remote Programming Software | |
| Remote Programming Software |
Parts Included
The D9124 Addressable Control Panel is shipped in three boxes. One box contains:
Quant. Component
1D9412GLTB Control Panel (less terminal blocks)
Another box contains:
Quant. Component
1D9101 Enclosure Assembly with Door
The third box contains a D9100 Accessory Module Carrier that includes the following:
Quant. Component
2D192C Indicating Circuit Supervision Modules
1D928 Dual Phone Line Switcher
1D8125 POPEX Module (additional optional)
1D9142LC 24 VDC Power Supply
The third box also contains:
Quant. Component
1D1256 Fire Alarm Keypad
1D1601 Transformer
1Wiring Harness
1Wiring Harness for the D8125 POPEX Module
2560 Ω Resistors (for D192C Modules)
2D161 Dual Modular Telephone Cords
1D162 Dual Modular Telephone Cord
1Literature pack
D9124 Addressable Fire Alarm Control Panel (FACP) 3
Technical Specifications
Environmental Considerations
Relative Humidity: |
| Up to 85%; |
Temperature (operating): | +32°F to +122°F (0°C to +50°C) | |
Inputs |
|
|
Sensor Circuits: |
| Up to two 8125 POPEX modules, |
|
| 119 addresses per module |
Sensor Circuit Protection: | Power limited to 4 A; short circuit, reverse | |
|
| polarity, thermal overload and current over- |
|
| load protection |
Sensor Loop Technology: | ||
Mechanical Properties |
|
|
Color: |
| Red |
Material: |
| |
Dimensions (H x W x D) |
| |
Enclosure Box: |
| 36.1 in. x 22.1 in. x 3.2 in. |
|
| (92 cm x 56 cm x 8.1 cm) |
Removable Door: |
| 37.1 in. x 23.3 in. x 1.1 in. |
|
| (94 cm x 59 cm x 2.8 cm) |
Outputs |
|
|
Up to 16 optional D8129 Relay Modules (eight re- | ||
| lay outputs per module) | |
Two; 1.8 A maximum per circuit | ||
Power Requirements |
|
|
Current (operating) |
|
|
Alarm + sensor load: |
| 874 mA |
Idle: |
| 412 mA |
Power (auxiliary): |
| 24 VDC nominal at 1.8 A |
Power (primary): |
| 120 VAC, 60 Hz, 360 VA |
Ordering Information
D9124 Addressable Fire Alarm Control | D9124 |
Panel (FACP) |
|
Up to eight supervised or 32 unsupervised re- |
|
mote annunciators |
|
Accessories |
|
D113 Battery Lead Supervision Module | D113 |
Supervises wiring connections for two 12 V |
|
batteries connected to the same set of charging |
|
terminals. |
|
D122 Dual Battery Harness | D122 |
Harness with circuit breaker. Connects two |
|
batteries to a compatible control panel. |
|
D135A Low‑battery Disconnect Module | D135A |
Disconnects the control panel from the battery |
|
when the battery level drops to 9.5 VDC. |
|
www.boschsecurity.com