2 FLM‑325‑IM Contact Module
Data Circuit Length
Data (or polling) circuit length is the distance over the circuit wire from the connection at the FACP to the most distant device and back to the FACP. Data circuit length must include the distance to any device connected to the circuit in a T tap. The screw terminals can accept up to 14 AWG (1.5 mm) wire, but this reduces the allowable length of the circuit.
Refer to the FPE‑1000‑SLC Installation Guide
(P/N: F01U078099) for specific wire instructions and specifications for the FPA‑1000 series panels.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL- listed normally open (NO) contact closure devices. Device circuit wiring must not exceed 50 Ω. Install contact closure devices according to the manufacturer’s installation instructions. All wiring must be supervised and
Note Do not mix fire alarm initiating and supervisory devices on the same module.
Mechanical |
|
Dimensions (H x W x D) | 2.375 in. x 1.75 in. x 0.5 in. |
| (60.325 mm x 44.45 mm x 12.7 mm) |
Weight | 20 oz (0.567 kg) |
Trademarks
Trademark names are used throughout this document. In most cases, these designations are claimed as trademarks or registered trademarks in one or more countries by their respective owners. Rather than placing a trademark symbol in every occurrence of a trademark name, Bosch Security Systems, Inc. uses the names only in an editorial fashion and to the benefit of the trademark owner with no intention of infringing the trademark.
Hochiki is a trademark of Hochiki America Corporation.
Ordering Information
FLM‑325‑IM Contact Module |
Allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit
Parts Included
Quant. Component
1Point contact module
1EOL resistor: Hochiki P/N 0400‑01046,. 10 kΩ, ¼ W, ¼ in.
1Literature – Installation Guide
Technical Specifications
Electrical |
|
SLC Applied Voltage (rated range): | 25.3 VDC to 39 VDC |
SLC Current Consumption: | Standby: 0.339 mA |
| Alarm: 0.358 mA |
Resistance |
|
End of Line Device | 10 kΩ, 0.25 W per resistor |
Initiating Device Circuit | Less than 50 Ω |
Environmental |
|
Environment: | Indoor dry |
Relative Humidity: | Up to 90%, non‑condensing |
Temperature: | Operating: 0°C to +49°C (+32°F to +120°F) |
| Storage: |
Americas: | Europe, Middle East, Africa: | Represented by | |
Bosch Security Systems, Inc. | Bosch Security Systems B.V. | Robert Bosch (SEA) Pte Ltd, Security Systems | |
130 Perinton Parkway | P.O. Box 80002 | 11 Bishan Street 21 |
|
Fairport, New York, 14450, USA | 5600 JB Eindhoven, The Netherlands | Singapore 573943 |
|
Phone: +1 800 289 0096 | Phone: + 31 40 2577 284 | Phone: +65 6258 5511 |
|
Fax: +1 585 223 9180 | Fax: +31 40 2577 330 | Fax: +65 6571 2698 |
|
security.sales@us.bosch.com | emea.securitysystems@bosch.com | apr.securitysystems@bosch.com |
|
www.boschsecurity.us | www.boschsecurity.com | www.boschsecurity.asia |
|
©Bosch Security Systems 2011 Data subject to change without notice T7621673227 Cur: