2 FLM325IM Contact Module

Data Circuit Length

Data (or polling) circuit length is the distance over the circuit wire from the connection at the FACP to the most distant device and back to the FACP. Data circuit length must include the distance to any device connected to the circuit in a T tap. The screw terminals can accept up to 14 AWG (1.5 mm) wire, but this reduces the allowable length of the circuit.

Refer to the FPE1000SLC Installation Guide

(P/N: F01U078099) for specific wire instructions and specifications for the FPA1000 series panels.

Initiating Device Circuit Connections

The initiating device circuit can use any number of UL- listed normally open (NO) contact closure devices. Device circuit wiring must not exceed 50 Ω. Install contact closure devices according to the manufacturer’s installation instructions. All wiring must be supervised and power-limited.

Note Do not mix fire alarm initiating and supervisory devices on the same module.

Mechanical

 

Dimensions (H x W x D)

2.375 in. x 1.75 in. x 0.5 in.

 

(60.325 mm x 44.45 mm x 12.7 mm)

Weight

20 oz (0.567 kg)

Trademarks

Trademark names are used throughout this document. In most cases, these designations are claimed as trademarks or registered trademarks in one or more countries by their respective owners. Rather than placing a trademark symbol in every occurrence of a trademark name, Bosch Security Systems, Inc. uses the names only in an editorial fashion and to the benefit of the trademark owner with no intention of infringing the trademark.

Hochiki is a trademark of Hochiki America Corporation.

Ordering Information

FLM325IM Contact Module

FLM-325-IM

Allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit

Parts Included

Quant. Component

1Point contact module

1EOL resistor: Hochiki P/N 040001046,. 10 kΩ, ¼ W, ¼ in.

1Literature – Installation Guide

Technical Specifications

Electrical

 

SLC Applied Voltage (rated range):

25.3 VDC to 39 VDC

SLC Current Consumption:

Standby: 0.339 mA

 

Alarm: 0.358 mA

Resistance

 

End of Line Device

10 kΩ, 0.25 W per resistor

Initiating Device Circuit

Less than 50 Ω

Environmental

 

Environment:

Indoor dry

Relative Humidity:

Up to 90%, noncondensing

Temperature:

Operating: 0°C to +49°C (+32°F to +120°F)

 

Storage: -30°C to +70°C (-22°F to +158°F)

Americas:

Europe, Middle East, Africa:

Asia-Pacific:

Represented by

Bosch Security Systems, Inc.

Bosch Security Systems B.V.

Robert Bosch (SEA) Pte Ltd, Security Systems

130 Perinton Parkway

P.O. Box 80002

11 Bishan Street 21

 

Fairport, New York, 14450, USA

5600 JB Eindhoven, The Netherlands

Singapore 573943

 

Phone: +1 800 289 0096

Phone: + 31 40 2577 284

Phone: +65 6258 5511

 

Fax: +1 585 223 9180

Fax: +31 40 2577 330

Fax: +65 6571 2698

 

security.sales@us.bosch.com

emea.securitysystems@bosch.com

apr.securitysystems@bosch.com

 

www.boschsecurity.us

www.boschsecurity.com

www.boschsecurity.asia

 

©Bosch Security Systems 2011 Data subject to change without notice T7621673227 Cur: en-US, V1, 25 May 2011

Page 2
Image 2
Bosch Appliances FLM325IM manual Ordering Information, Parts Included, Technical Specifications