The connection to a Building Management System (BIS) is done via an OPC server and the Ethernet 100BaseTX interface. For a multiple-building network, you must check with the network adminstrator if

the network is designed for multiple-building connections (e.g. no technical interference by varying ground potentials)

the bus users are designed for the network

Address Setting and Configuration

1.Assign a unique physical address to each Panel Controller and Remote Keypad by setting the rotary switches and write it down on the label (Step 1 and 2, Figure 7, Page 9). Make sure that the redundant panels do have identical addresses.

2.For configuration, set the 6-pin DIP switch (Step 3, Figure 7, Page 9).

3.Mark the setting on the provided label (Step 4).

Note the DIP switch and address settings for the stand-alone and redundant configuration (Figure 9, Page 10).

NOTICE!

DIP 6 on the Panel Controller of the FPA-1200 is inoperable, as it cannot be operated as a redundant panel.

Technical Specifications

LCD display / touch screen

320 x 240 pixels / 127.5 mm x 170 mm active surface

 

 

Operating and display elements

22 keys, 1 key switch, 11 LEDs, 1 reboot button

 

 

Interfaces

CAN1, CAN2, ETH1, ETH2, USB, RS232

 

 

Signal inputs

IN1/IN2

 

 

Max. CAN cable length in networks

Lmax = 1000 m, depending on configuration, cable type and topology

Input voltage

20 V DC to 30 V DC

 

 

Power supply PRS 0002 A

+5 V DC ±4.5 % / max. 500 mA

 

 

 

Max. current consumption

-

Standby: 135 mA at 24 V DC

 

-

During alarm: 225 mA at 24 V DC

 

 

Permissible operating temperature

-5 °C to +50 °C

 

 

Permissible storage temperature

-20 °C to +70 °C

 

 

Dimensions (H x W x D)

190 mm x 404 mm x 60 mm

 

 

Weight

Approx. 2 kg

 

 

 

F.01U.258.925 2.0 2012.04