8 Grounding Maintenance and upkeep Disposal | en |
|
|
en | Specification I Wiring 9 |
|
|
Notes on Installation
Clearance between the module frame and the mount- ing surface is required to allow cooling air to circu- late around the back of the module. This also allows any condensation or moisture to dissipate. The mod- ule should never be sealed to the mounting surface with sealant that prevents air from circulating under the module.
Leave 4 inches of clearance between the roof and the module frame.
Refer to your local authority for guidelines and re- quirements for building or structural fire safety.
For roof application, the modules should be mounted over a fire resistant covering rated for the application
Standard Operating Condition
Bosch Solar Energy AG recommends that modules be operated under Standard Operating Conditions (SOC). An installation location with conditions exceeding SOC or with other Special Conditions (see below) should be avoided. SOC of Bosch Solar Energy AG modules is as follows:
1. Standard Operating Conditions (SOC)
The modules should be operated only in terrestrial applications. No space or other Special Conditions (see below).
The measured ambient temperature of the installa- tion location should be within
The lower and upper temperature limit is defined as the monthly average low or high of the installation location.
The relative humidity should be within 45 % to 95 %.
The installation place should be less than 1,000 m (3,280ft) above sea level.
Installations more than 1,000 m (3,280 ft) are allowed only if the wind pressure load for a module is less than 2,400N/m2 (50PSF).
2. Special Conditions
The ambient temperature of the installation place exceeds SOC.
The salt damage is heavy at the installation place.
The hail and snow damage is heavy at the installation place.
The sand and dust damage is heavy at the installation place.
The air pollution, chemically active vapors, acid rain, and/or soot, etc. are heavy at the installation place
3. Application Class & Safety Class
The modules are qualified for application class A: Haz- ardous voltage (IEC 61730:Higher than 50VDC; EN 61730: Higher than 120 V), hazardous power applica- tions (Higher than 240 W) where general contact access is anticipated (modules qualified for safety through EN
6 Specification
60 Cell Module Series
| Model Number | IN30125 – 225 | |
|
|
|
|
| Peak / Rated Power (Pmax, Wp) | 225 |
|
|
|
|
|
| Max Power Voltage (Vmp, V) | 29.40 |
|
|
|
|
|
| Max Power Current (Imp, A) | 7.80 |
|
|
|
|
|
| Open Circuit Voltage (Voc, V) | 36.90 |
|
|
|
|
|
| Short Circuit Current (Isc, A) | 8.30 |
|
|
|
|
|
| Power Tolerance (%) | ± 3 |
|
|
|
|
|
| Factory Installed Bypass Diode (Qty) | 3 |
|
|
|
|
|
| Bypass Diode Rating (A) | 15 |
|
|
|
|
|
| Max. Series Fuse Rating (Amps) | 15 |
|
|
|
|
|
| Maximum System Voltage (VDC) | 1000 |
|
|
|
|
|
| Fire Resistance Rating | Class C | |
|
|
|
|
| Temp. coefficient of Voc (%/ºC) |
| |
|
|
|
|
| Temp. coefficient of Isc (%/ºC) | 0.032 |
|
|
|
|
|
| Temp. coefficient of Pmax (%/ºC) |
| |
|
|
|
|
| Cable (1Mtr | 4Sq.mm, 12AWG | |
|
|
|
|
| Length, mm (Inches) | 1660(65.35) |
|
|
|
|
|
| Width, mm (Inches) | 990(43.92) |
|
|
|
|
|
| Frame Depth(Thk), mm (Inches) | 42 (1.65) |
|
|
|
|
|
| Weight, Kg (Pounds) | 20(44.09) |
|
|
|
|
|
| Mounting Hole, mm (inches) | 8x12 (0.315x0.472), | |
|
| Qty- 8 | |
|
|
|
|
| Ground Hole dia., mm (Inches) | Ground back – 5mm | |
|
| (0.196) dia., | |
|
|
|
|
Note: Modules in parallel can be done as applicable
Notes:
1.Rated electrical characteristics are within 10 % of the values measured at Standard Test Conditions (STC) of: 1000W/m2, 25ºC cell temperature and solar special irradiance per IEC
7Wiring
Important Notice!
General |
|
|
|
|
All wiring should be done in accordance with applicable | english | |||
electrical codes. |
|
|
| |
|
|
|
| |
All wiring should be done by a qualified, licensed |
| |||
professional. Wiring should be protected to help |
| |||
| ||||
ensure personal safety and to prevent its damage. |
| |||
All Bosch Solar Energy AG modules are equipped |
| |||
with wires and quick connectors. Modules have been |
| |||
designed to be easily interconnected in series. |
| |||
Modules can be wired in series to increase voltage. |
| |||
Connect wires from positive terminal of one module |
| |||
to the negative terminal of the next module. All mod- |
| |||
ules connected in series should be of the same |
| |||
model number and/or type. Make sure the number of |
| |||
modules connected in series does not exceed: ((Max- |
| |||
imum system voltage / Open circuit voltage of the |
| |||
module) – 1) at standard condition, AM1.5G, 25 |
| |||
degrees temperature, 1,000 W/m2. |
| |||
Connect modules in parallel to increase current. |
| |||
Connect wires from the positive terminal of the one |
| |||
module to the positive terminal of the next module. |
| |||
Do not connect modules in parallel without using a |
| |||
connection box. The number of parallel strings de- |
| |||
pends on the system integrator’s requirements and |
| |||
the inverter ratings. |
|
|
| |
These modules contain factory installed bypass |
| |||
diodes. If these modules are incorrectly connected to |
| |||
each other, the bypass diodes, cables, or junction |
| |||
box may be damaged. |
|
|
| |
|
|
|
|
|
Module | Positive Pole | Negative Pole |
| |
Version |
|
|
|
|
|
|
|
|
|
IN xx125 | Tyco, Neutral | Tyco, Minus |
| |
|
|
| ||
|
|
|
|
|
Coding for connector plug1
1IN xxxxx: Internal technology code
Bosch Solar Module | Bosch Solar Energy AG | Bosch Solar Module | Bosch Solar Energy AG |