Bosch Appliances IN30125 Specification, Wiring, Grounding Maintenance and upkeep Disposal

Models: IN30125

1 7
Download 7 pages 53.53 Kb
Page 5
Image 5
8  Grounding  Maintenance and upkeep  Disposal

8 Grounding Maintenance and upkeep Disposal

en

 

 

en

Specification I Wiring 9

 

 

Notes on Installation

Clearance between the module frame and the mount- ing surface is required to allow cooling air to circu- late around the back of the module. This also allows any condensation or moisture to dissipate. The mod- ule should never be sealed to the mounting surface with sealant that prevents air from circulating under the module.

Leave 4 inches of clearance between the roof and the module frame.

Refer to your local authority for guidelines and re- quirements for building or structural fire safety.

For roof application, the modules should be mounted over a fire resistant covering rated for the application

Standard Operating Condition

Bosch Solar Energy AG recommends that modules be operated under Standard Operating Conditions (SOC). An installation location with conditions exceeding SOC or with other Special Conditions (see below) should be avoided. SOC of Bosch Solar Energy AG modules is as follows:

1. Standard Operating Conditions (SOC)

The modules should be operated only in terrestrial applications. No space or other Special Conditions (see below).

The measured ambient temperature of the installa- tion location should be within –20º C (-4° F) to 40º C (104° F).

The lower and upper temperature limit is defined as the monthly average low or high of the installation location.

The relative humidity should be within 45 % to 95 %.

The installation place should be less than 1,000 m (3,280ft) above sea level.

Installations more than 1,000 m (3,280 ft) are allowed only if the wind pressure load for a module is less than 2,400N/m2 (50PSF).

2. Special Conditions

The ambient temperature of the installation place exceeds SOC.

The salt damage is heavy at the installation place.

The hail and snow damage is heavy at the installation place.

The sand and dust damage is heavy at the installation place.

The air pollution, chemically active vapors, acid rain, and/or soot, etc. are heavy at the installation place

3. Application Class & Safety Class

The modules are qualified for application class A: Haz- ardous voltage (IEC 61730:Higher than 50VDC; EN 61730: Higher than 120  V), hazardous power applica- tions (Higher than 240 W) where general contact access is anticipated (modules qualified for safety through EN 61730-1 and 61730-2 within this application class are considered to meet the requirement for Safety Class II).

6 Specification

60 Cell Module Series

 

Model Number

IN30125 – 225

 

 

 

 

 

Peak / Rated Power (Pmax, Wp)

225

 

 

 

 

 

 

Max Power Voltage (Vmp, V)

29.40

 

 

 

 

 

 

Max Power Current (Imp, A)

7.80

 

 

 

 

 

 

Open Circuit Voltage (Voc, V)

36.90

 

 

 

 

 

 

Short Circuit Current (Isc, A)

8.30

 

 

 

 

 

 

Power Tolerance (%)

± 3

 

 

 

 

 

 

Factory Installed Bypass Diode (Qty)

3

 

 

 

 

 

 

Bypass Diode Rating (A)

15

 

 

 

 

 

 

Max. Series Fuse Rating (Amps)

15

 

 

 

 

 

 

Maximum System Voltage (VDC)

1000

 

 

 

 

 

 

Fire Resistance Rating

Class C

 

 

 

 

 

Temp. coefficient of Voc (%/ºC)

-0.32

 

 

 

 

 

 

Temp. coefficient of Isc (%/ºC)

0.032

 

 

 

 

 

 

Temp. coefficient of Pmax (%/ºC)

-0.46

 

 

 

 

 

 

Cable (1Mtr Length-2Nos)

4Sq.mm, 12AWG

 

 

 

 

 

Length, mm (Inches)

1660(65.35)

 

 

 

 

 

 

Width, mm (Inches)

990(43.92)

 

 

 

 

 

 

Frame Depth(Thk), mm (Inches)

42 (1.65)

 

 

 

 

 

 

Weight, Kg (Pounds)

20(44.09)

 

 

 

 

 

 

Mounting Hole, mm (inches)

8x12 (0.315x0.472),

 

 

Qty- 8

 

 

 

 

 

Ground Hole dia., mm (Inches)

Ground back – 5mm

 

 

(0.196) dia., Qty-2

 

 

 

 

Note: Modules in parallel can be done as applicable

Notes:

1.Rated electrical characteristics are within 10 % of the values measured at Standard Test Conditions (STC) of: 1000W/m2, 25ºC cell temperature and solar special irradiance per IEC 60904-3.

7Wiring

Specification I Wiring  9 Important Notice!

General

 

 

 

 

All wiring should be done in accordance with applicable

english

electrical codes.

 

 

 

 

 

 

 

All wiring should be done by a qualified, licensed

 

professional. Wiring should be protected to help

 

 

ensure personal safety and to prevent its damage.

 

All Bosch Solar Energy AG modules are equipped

 

with wires and quick connectors. Modules have been

 

designed to be easily interconnected in series.

 

Modules can be wired in series to increase voltage.

 

Connect wires from positive terminal of one module

 

to the negative terminal of the next module. All mod-

 

ules connected in series should be of the same

 

model number and/or type. Make sure the number of

 

modules connected in series does not exceed: ((Max-

 

imum system voltage / Open circuit voltage of the

 

module) – 1) at standard condition, AM1.5G, 25

 

degrees temperature, 1,000 W/m2.

 

Connect modules in parallel to increase current.

 

Connect wires from the positive terminal of the one

 

module to the positive terminal of the next module.

 

Do not connect modules in parallel without using a

 

connection box. The number of parallel strings de-

 

pends on the system integrator’s requirements and

 

the inverter ratings.

 

 

 

These modules contain factory installed bypass

 

diodes. If these modules are incorrectly connected to

 

each other, the bypass diodes, cables, or junction

 

box may be damaged.

 

 

 

 

 

 

 

 

Module

Positive Pole

Negative Pole

 

Version

 

 

 

 

 

 

 

 

 

IN xx125

Tyco, Neutral

Tyco, Minus

 

 

6-1394461-2

0-1394462-4

 

 

 

 

 

 

 

Coding for connector plug1

1IN xxxxx: Internal technology code

Bosch Solar Module c-Si M 60 IN30125

      Bosch Solar Energy AG

Bosch Solar Module c-Si M 60 IN30125

      Bosch Solar Energy AG

Page 5
Image 5
Bosch Appliances IN30125 Grounding Maintenance and upkeep Disposal, Specification I Wiring, Notes on Installation