Bosch Appliances tc9346a instruction manual Table A. 24 VAC Wiring Distances, Wire Gauge

Models: tc9346a

1 16
Download 16 pages 54.06 Kb
Page 10
Image 10
Table A. 24 VAC Wiring Distances

EXAMPLE: An enclosure that re- quires 80 vA and is installed 35 feet (10 m) from the transformer would require a minimum wire gauge of 20 AWG.

NOTE: Distances are calculated in feet; values in parentheses are meters.

Table A. 24 VAC Wiring Distances

The following are the recommended maximum distances for 24 VAC applications and are calculated with a 10-percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC-powered devices.)

Wire Gauge

 

 

20

18

16

14

12

10

 

 

 

 

 

 

 

 

 

 

 

10

283

451

716

1142

1811

2880

 

 

 

(86)

(137)

(218)

(348)

(551)

(877)

 

 

 

 

 

 

 

 

 

 

 

20

141

225

358

571

905

1440

 

 

 

(42)

(68)

(109)

(174)

(275)

(438)

 

 

 

 

 

 

 

 

 

 

 

30

94

150

238

380

603

960

 

 

 

(28)

(45)

(72)

(115)

(183)

(292)

 

 

 

 

 

 

 

 

 

 

 

40

70

112

179

285

452

720

 

 

 

(21)

(34)

(54)

(86)

(137)

(219)

 

 

 

 

 

 

 

 

 

 

 

50

56

90

143

228

362

576

 

 

 

(17)

(27)

(43)

(69)

(110)

(175)

 

 

 

 

 

 

 

 

 

 

 

60

47

75

119

190

301

480

 

 

 

(14)

(22)

(36)

(57)

(91)

(146)

 

 

 

 

 

 

 

 

 

loadto

 

80

35

56

89

142

226

360

 

70

40

64

102

163

258

411

 

 

 

(12)

(19)

(31)

(49)

(78)

(125)

 

 

 

(10)

(17)

(27)

(43)

(68)

(109)

fromdistancetransformer

consumedvATotal

 

 

 

 

 

 

 

130

21

34

55

87

139

221

 

90

31

50

79

126

201

320

 

 

 

(9)

(15)

(24)

(38)

(61)

(97)

 

 

100

28

45

71

114

181

288

 

 

 

(8)

(13)

(21)

(34)

(55)

(87)

 

 

110

25

41

65

103

164

261

 

 

 

(7)

(12)

(19)

(31)

(49)

(79)

 

 

 

 

 

 

 

 

 

 

 

120

23

37

59

95

150

240

 

 

 

(7)

(11)

(17)

(28)

(45)

(73)

 

 

 

 

 

 

 

 

 

 

 

 

(6)

(10)

(16)

(26)

(42)

(67)

Maximum

 

 

 

 

 

 

 

 

 

150

18

30

47

76

120

192

 

140

20

32

51

81

129

205

 

 

 

(6)

(9)

(15)

(24)

(39)

(62)

 

 

 

(5)

(9)

(14)

(23)

(36)

(58)

 

 

 

 

 

 

 

 

 

 

 

160

17

28

44

71

113

180

 

 

 

(5)

(8)

(13)

(21)

(34)

(54)

 

 

 

 

 

 

 

 

 

 

 

170

16

26

42

67

106

169

 

 

 

(4)

(7)

(12)

(20)

(32)

(51)

 

 

 

 

 

 

 

 

 

 

 

180

15

25

39

63

100

160

 

 

 

(4)

(7)

(11)

(19)

(30)

(48)

 

 

 

 

 

 

 

 

 

 

 

190

14

23

37

60

95

151

 

 

 

(4)

(7)

(11)

(18)

(28)

(46)

 

 

 

 

 

 

 

 

 

 

 

200

14

22

35

57

90

144

 

 

 

(4)

(6)

(10)

(17)

(27)

(43)

 

 

 

 

 

 

 

 

 

 

10