Bradford-White Corp TG237E-N(X), TG-237E-N(X)A Section Viii Maintenance, Burner Flame Appearance

Models: TG-199E-N(X) TG237E-N(X) TG-180E-N(X) TG-150E-N(X) TG-237E-N(X)A

1 72
Download 72 pages 2.21 Kb
Page 47
Image 47

SECTION VIII: MAINTENANCE

WARNING

Always turn off the electrical power supply, the manual gas valve, and the manual water control valve whenever servicing this appliance.

KEEP THE WATER HEATER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.

The EverHot® water heater should be checked annually by a qualified technician. Regular maintenance will keep the water heater operating efficiently and help to assure reliable operation and a long service life.

1.Remove and clean the inlet water filter screen. If a Y-type strainer or cartridge filter is used on the cold water inlet to the water heater, inspect or clean as needed to assure full water flow to the water heater.

2.Visually inspect the burner flames. The flame must burn with a clear blue, stable flame (possibly with orange tips). Refer to Figure 19 for satisfactory flame appearance. If the burner flame appearance is not satisfactory or debris is visible on the burners, remove and clean with a vacuum cleaner.

Figure 19. Burner Flame Appearance.

3.Check the front vent outlet for blockage and clean, if necessary. Keep shrubs and vegetation clear of the vent terminal.

4.All electric motors are permanently lubricated and do not need oiling. Remove the combustion air blower and clean wheel and housing with soft brush or vacuum.

5.If the “LC” code has been flashing on the display, the heat exchanger will need flushing to remove lime and scale deposits. Refer to the “Flushing Procedure for Lime Scale Removal…” in Section VIII, “Maintenance.”

6.Check operation of the pressure relief valve. To check the relief valve, lift the lever at the end of the valve several times. The valve should seat properly and operate freely. If water does not flow, remove and inspect for obstructions or corrosion. Replace with a new valve of the recommended size as necessary. A thorough inspection of the valve should be performed at least every three years by removing the pressure relief valve from the outlet piping. Do not attempt to repair the valve, as this could result in improper operation and explosion of the heat exchanger and piping. In areas with poor water conditions, it may be necessary to inspect the pressure relief valve more often than the recommended maintenance schedule.

47

Page 47
Image 47
Bradford-White Corp TG237E-N(X), TG-237E-N(X)A, TG-150E-N(X), TG-180E-N(X) Section Viii Maintenance, Burner Flame Appearance