Bravo View B409 G - Concrete and Backfill Guidelines, Minimum 4 inches, Soil, Sump Cover

Models: B409

1 12
Download 12 pages 5.43 Kb
Page 12
Image 12
G - Concrete and Backfill Guidelines.

G - Concrete and Backfill Guidelines.

To ensure that no immediate or future damage is done to your Bravo Tank Sump Reducer components, make sure that your manhole skirt DOES NOT TOUCH OR REST ON THE TANK SUMP SHOULDER. The Manhole Skirt should be kept at minimum of 4” away from the tank sump shoulder. Follow the manhole manufacturers instructions for installing the manhole. Also follow other details provided by tank and/or engineering firm for tank driveway pad installation.

Backfill your peagravel around the sump maintaining a minimum of 1’ foot all the way around (if your site backfill is not entirely peagravel) and 4” minimum distance from the top edge of sump reducer.

When peagravel is in place, use a 3mil or thicker plastic sheet to cover the surface of the peagravel no less than 2 feet away from the sump reducer wall.

Secure this plastic barrier to the EXTERIOR OF THE MANHOLE SKIRT using duct tape. This prevents concrete from seeping too far down

into the peagravel.

Minimum 4 inches

between top of sump reducer and peagravel

3mil+ Plastic Barrier

taped to manhole skirt

Manhole Cover

Manhole skirt

CONCRETE

SLAB

SOIL

 

 

 

 

 

Sump Cover

 

 

 

 

 

 

 

 

 

 

Min 1’ foot

 

ORSAND

peagravel all

 

around sump

 

 

 

 

 

 

 

 

1” to 1-1/2” Minimum 4 inches Distance

Manhole skirt min. 4” away from Tank sump shoulder

12ii-B409-DW-10A

Page 12
Image 12
Bravo View B409 G - Concrete and Backfill Guidelines, Minimum 4 inches, Soil, 1” to 1-1/2” Distance, Sump Cover