Equivalent Vent Length (EVL)

INSTALLATION

7

Equivalent Vent Length (EVL)

The longer the run of pipe in your installation (both with inserts and freestandings), the more restriction there is in the system. Therefore, larger diameter pipe should be used.

Use 4” pipe if you have more than 15 feet of equivalent vent length.

Horizontal runs shall not exceed 10 feet of EVL.

It is recommended that vertical runs be a minimum of 8 feet.

To calculate EVL, use the following conversions:

90º elbow or “T”

= 5 equivalent feet

45º elbow

= 3 equivalent feet

Horizontal Pipe Run

= 1 equivalent foot per actual foot

Vertical Pipe Run

= 0.5 equivalent foot per actual foot

NOTE: At altitudes above 3,000 feet, we suggest the use of 4” diameter vent at an EVL of 7 feet or more.

FREESTANDING INSTALLATIONS

A.ASSEMBLING PEDESTAL OR LEG SET

If using a pedestal, follow the instructions inside the Breckwell P22 Pedestal Set Part # A-22-P (refer to figure 8).

If using cast legs, follow the instructions inside the Breckwell P22 Leg Set Part # A-CGL-22 or # A-CL-22.

Legs are installed by using the four bolts provided in the kit into the four holes under the stove at each corner, thread on nuts from the top and tighten. Make sure to save the hole plugs.

NOTE: If converting from legs to pedestal the hole plugs must be installed in the unused holes.

B.HORIZONTALLY THROUGH WALL (refer to Figure 9)

NOTE: Follow L-Vent chimney manufacturer’s instructions.

1.Position stove, adhering to clearances shown in Figures 1 & 2.

2.Locate position of hole in wall; directly behind stove exhaust vent (refer to figure 5).

3.Always maintain 3” clearance from combustible materials.

4.Install L-Vent wall thimble per L-Vent manufacturer’s instructions.

5.Attach enough piping to penetrate and extend at least 6” beyond exterior walls. An 8-foot vertical pipe run is suggested where possible to reduce the possibility of smoke spillage in the event of a loss of negative pressure.

6.Attach cap and seal outside wall thimbles with non-hardening waterproof mastic.

7.Termination should not be located so that hot exhaust gases can ignite trees, shrubs, or grasses or be a hazard to children. Exhaust gases can reach temperatures of 500ºF and cause serious burns if touched.

FIGURE 8

FIGURE 9

Locate terminations: a) not less than 3 feet above any forced air inlet located within 10 feet; b) not less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air inlet into any building; c) not less than two feet from an adjacent building and not less than 7 feet above grade when located adjacent to a public walkway. Mobile home installations must use a spark arrester.