INSTALLATION
The generator weighs more than 280 pounds. Proper tools, equipment and qualified personnel should be used in all phases of handling and moving generator.
WARNING
Lifting Hazard / Heavy Object
Can cause muscle strain or back injury.
•DO NOT lift or move generator without assistance.
•DO NOT lift unit by roof as damage to generator will occur.
Lifting pockets are provided at each corner between the base of the generator and its mounting pad. Retouch any chipped paint with supplied
Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.
WARNING
Exhaust heat/gases can ignite combustibles or structures causing a fire.
•DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.
•Keep at least 3 ft. (91 cm) clearance on all sides of generator including overhead.
Generator ClearancesInstall generator outdoors in an area which will not accumulate deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 1). Prevailing winds and air currents should be taken into consideration when positioning generator.
Figure 1 — Home Standby Generator Clearances
Exhaust
Port
WARNING
Running engine gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting or death.
•Operate generator ONLY outdoors.
•Install a battery operated carbon monoxide alarm near the bedrooms.
•Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.
General Location Guidelines•Install the unit outdoors ONLY.
•Place the unit in a prepared location that is flat and has provisions for water drainage.
•Install the unit in a location where sump pump discharge, rain gutter down spouts, roof
•Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.
•Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.
•Install the generator as close as possible to the fuel supply to reduce length of pipes.
IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.
The Home Standby Generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.
If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.
10