Maintenance

Testing Your GenAlert

Testing programmed phone number.
Press and hold the star (*) key until you see the
red LED light up.
Release the star key.
GenAlert will call the programmed number and play
the prerecorded alarm message. Canceling the alarm
for this test is not required.
Testing GenAlert Alarm.
The alarm goes off when the generator fails to
run when it is needed. To simulate this failure the
generator needs to be running to see the fault, then
shuts down, followed by the GenAlert calling the
programed number.
Simulate a fault by turning the generator circuit
breaker to the off position. The generator should
shut down and display the fault.
The red LED will light up and GenAlert will then
call the programmed number and indicate an
alarm.
1.
2.
1.
2.
Test Failure
If the test fails, first try reprogramming the phone
number and repeat the test. If a test failure persists,
refer to Troubleshooting.

Battery Replacement

Replace the battery every year.
GenAlert does not notify for “low battery” conditions.
Remove battery when the unit is not in use.