Troubleshooting
Problem | Cause | Correction | ||
Automatic transfer switch does not | 1. | Generator breaker open. | 1. | Reset generator circuit breaker. |
transfer to generator | 2. | Generator voltage not acceptable. | 2. | Refer to generator manual. |
|
|
|
|
|
| 1. | Utility disconnect circuit breaker | 1. | Reset utility disconnect circuit |
Automatic transfer switch does not |
| open. |
| breaker. |
transfer to utility | 2. | Utility voltage not acceptable. | 2. | Wait for utility voltage to return to |
|
|
|
| normal. |
|
|
| ||
Generator is still running after switch | Engine cool down period. | Engine should stop after 1 minute. | ||
transfers to utility power |
|
|
|
|
|
|
|
|
|
| 1. | Minimum engine run time has not | 1. | Wait five minutes for transfer |
Generator is still running after utility |
| elapsed. |
| switch to retransfer to utility power. |
power is restored | 2. | Fuse(s) in transfer switch is | 2. | Check fuse(s) and replace if |
|
| defective. |
| necessary. |
|
|
|
|
|