GENERAL REQUIREMENTS AND SPECIFICATIONS (CONT’D)

GENERAL REQUIREMENTS AND SPECIFICATIONS (CONT’D)

 

 

 

240 VOLTS – SINGLE PHASE

 

 

TEMP. RISE @ 0.20 IN. W.C.

 

 

 

 

 

 

 

 

 

 

 

 

MODEL NO.

KW

 

BTUH

AMPS INCL. MOTOR

 

HP

BLOWER

°C

°F

*SPEED

RPM

 

 

 

 

 

 

 

 

 

 

 

 

21D10

10

 

34120

46

 

1/3

 

21

70

MED-LOW

814

 

 

 

 

 

 

 

 

 

 

 

 

21D15

15

 

51180

67

 

1/3

 

24

25

MED-LOW

814

 

 

 

 

 

 

 

 

 

 

 

 

21D18

18

 

61420

77

 

1/3

10” x 8”

27

81

MED-LOW

814

21D20

20

 

68240

86

 

1/3

(254 mm x 203 mm)

33

91

MED-LOW

814

 

 

 

 

 

 

 

 

 

 

 

 

21D23

22.5

 

76842

94

 

1/3

 

36

97

MED-LOW

814

 

 

 

 

 

 

 

 

 

 

 

 

21D25

25

 

85003

107

 

1/3

 

37

99

MED-LOW

814

 

 

 

 

 

 

 

 

 

 

 

 

21D27

27

 

92130

116

 

3/4

12” x 8”

36

97

MED-HI

707

 

 

(304 mm x 203 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*FACTORY SETTINGS.

 

 

 

 

 

 

 

 

 

SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

10” x 8” (254 mm x 203 mm) BLOWER

 

FLOW

 

STATIC PRESSURE

 

SPEED

(INCHES OF WATER COLUMN)

RATE

 

 

 

 

 

 

 

 

0.2

0.3

0.4

0.5

0.6

 

 

 

 

 

 

 

LOW**

CFM

756

749

740

729

713

L/s

357

353

349

344

337

 

 

 

 

 

 

 

 

MED-LOW

CFM

1035

1018

997

971

935

L/s

488

480

470

458

441

 

 

 

 

 

 

 

 

MED-HIGH

CFM

1177

1157

1132

1102

1063

L/s

556

546

534

520

502

 

 

 

 

 

 

 

 

HIGH

CFM

1301

1276

1247

1207

1145

L/s

614

602

588

569

540

 

 

 

 

 

 

 

 

WARNING:

12” x 8” (304 x 203 mm) BLOWER

 

FLOW

 

STATIC PRESSURE

 

SPEED

(INCHES OF WATER COLUMN)

RATE

 

 

 

 

 

 

 

 

0.2

0.3

0.4

0.5

0.6

 

 

 

 

 

 

 

LOW**

CFM

727

699

667

636

606

L/s

343

330

315

300

286

 

 

 

 

 

 

 

 

MED-LOW**

CFM

912

897

878

853

823

L/s

431

423

414

402

388

 

 

 

 

 

 

 

 

MED-HIGH

CFM

1216

1200

1181

1157

1129

L/s

574

566

557

546

533

 

 

 

 

 

 

 

 

HIGH

CFM

1640

1601

1558

1513

1466

L/s

774

755

735

714

692

 

 

 

 

 

 

 

 

**These speeds can only be run with heater off, for cooling/ventilation purposes only.

OPERATING OPTIONS

The furnace is shipped from the factory in a “Standard Heating Mode” (all switches in the Down position). When the thermostat calls for heat, the automatic controls will be activated and the furnace turns “ON”.

The blower will run at low speed or higher speed (as selected by

SPEED SELECTOR switch).

HIGH

LOW

SPEED SELECTOR

As the furnace heats up, it automatically switches to a medium speed when additional elements are activated by the electronic control, if it was initially set to run at low speed. The timing of this blower speed change will depend on whether COLD or MILD is selected on the SEASON SELECT switch.

You may, however, change from the Standard Heating Mode by using the controls built into your furnace.

MILD

COLD

SEASON SELECT

The SPEED SELECTOR switch is used to control the fan speed

During spring or fall, you may require less rapid response when

(ventilation). Even if there is no call for heat, the ventilation can be

the thermostat calls for heat.

 

controlled by the thermostat; the fan speed is determined by this

When MILD is selected, it takes more time to bring all the elements online.

switch.

When COLD is selected, the heating elements come online faster.

LOW – The blower motor will operate at low speed.

 

 

 

 

 

 

MILD SEASON (First Stage)

 

COLD SEASON (Second Stage)

HIGH – The blower motor will operate at a higher speed.

 

 

 

Slow Response Sequence

 

Rapid Response Sequence

 

 

 

 

 

 

 

Element 1 - Heat on instantly

 

Element 1 - Heat on instantly

 

 

 

 

 

 

 

Blower on after 3 seconds delay

 

Blower on after a 3 seconds delay

 

 

 

 

Elements 3 and 5 after 1 minute delay

Elements 3 and 5 after 10 seconds delay

 

 

 

 

 

 

 

Element 2 after 2 minutes delay

 

Element 2 after 20 seconds delay

 

 

 

 

Elements 4 and 6 after 3-minute delay

Elements 4 and 6 after 30 seconds delay

 

 

 

 

NOTE: Elements 4, 5 and 6 only where applicable.