Broan ERV90HCS, HRV90HS 6WIRINGDIAGRAM, disconnect, 120V, 60Hz, from, power, Color Code

Models: ERV90HC HRV90HS HRV90H ERV90HCS

1 26
Download 26 pages 38.21 Kb
Page 20
Image 20
ofRiskelectrical shocks. Before

 

 

 

 

WIRING DIAGRAM

 

 

 

 

 

 

 

LOGIC DIAGRAM

 

 

 

ofRiskelectrical shocks. Before

.6WIRINGDIAGRAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 V, 60Hz

 

 

 

 

120V, 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J10-2

 

 

A1

 

J10-1

 

 

Line voltage factory wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1

 

 

 

 

 

 

 

Class 2 low voltage factory wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class 2 low voltage field wiring

 

 

 

 

 

 

 

 

 

 

K2

K1

 

Exhaust fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J9-1

 

 

 

 

 

M3

 

BK

J3

A2

 

DAMPER

 

 

J9-2 nc

 

 

J5-1

 

J5-2

 

 

 

 

 

 

1 2

2 1

 

 

 

J9-3

 

 

J5-3

 

 

 

 

 

 

 

 

BK

5 4 3 2 1

 

ELECTRONIC ASSEMBLY

 

 

 

 

 

 

 

 

performing

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

Exhaust fan motor

 

 

 

 

 

Damper motor

J1

 

 

 

 

 

J9-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacitor

 

 

 

 

 

 

 

 

S1

 

 

 

 

 

 

 

 

 

 

J7-2

 

 

 

 

 

 

 

 

 

 

 

 

Defrost

 

 

 

 

 

 

 

 

 

 

 

 

T1

Door interlock switch

 

 

 

 

 

 

 

 

 

J7-1

 

 

 

 

 

 

 

 

 

 

 

temperature sensor

 

 

 

 

 

 

 

 

 

 

 

BK 120 V

(magnetically actuated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 V

reed switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BL

90 V

 

 

 

R1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3

 

Supply fan motor

 

 

 

 

R

68 V

class 2

 

 

 

 

 

 

 

 

 

 

 

any

 

 

 

 

 

9.5 V

 

 

 

 

 

 

 

 

 

 

 

 

J4-1

 

J4-2

 

 

 

 

 

 

 

 

 

 

 

 

Field wiring

 

 

 

 

 

 

 

 

 

 

W neutral

W

W

 

 

 

 

 

 

 

 

 

J4-3

 

 

 

 

 

class 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y BN

 

 

 

 

 

remote control

 

 

 

 

 

Supply fan motor

maintenance or servicing,

 

 

 

 

 

 

 

 

 

 

(see notes 3 & 4)

 

 

 

 

 

 

 

 

G

 

 

Y

BN

 

 

 

 

 

 

 

 

 

 

 

J6-2

capacitor

 

 

 

 

 

 

 

 

 

 

 

 

B G R Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J6-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

! WARNING

 

Exhaust fan

 

BK

J5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor

M1

BL BN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

J8

 

 

10

 

 

 

 

 

 

 

 

 

 

- 20 -

Exhaust fan

 

 

2

 

J11

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

J13

8

 

 

Override

 

 

 

 

J12-5

J2-5

 

 

motor

 

BK

2

5 4 3 2 1

1 2

7

 

 

 

 

 

 

A2

 

C1

ICP

6

 

 

switch

 

 

 

 

J12-4

J2-4

 

capacitor

BK

1

 

 

J12

5

 

 

 

 

 

 

 

 

 

J7

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5

 

3

 

 

(optional; see

 

 

 

K4

J12-3

J2-3

 

Damper motor

 

 

 

 

J9

 

 

2

 

 

 

 

 

 

Supply fan

 

BK

J6

See note 6

 

1

 

 

notes 3 & 4)

120 V

 

J8-1

 

J12-2

J2-2

J3-2

 

 

 

 

J14

 

 

 

 

motor

C2

BK

2

4 3 2 1

 

 

 

 

 

90 V

24 V

J8-2

 

J12-1

J2-1

J3-1

 

1

 

 

 

 

 

 

 

 

capacitor

 

 

1 See note 1 2

1

 

 

 

 

 

 

68 V

class 2

J8-4

 

 

 

Door interlock switch

 

 

BK

2

F1 J10

 

ELECTRONIC

 

 

 

 

9.5 V

 

 

J11-2

 

Supply fan

 

3

 

 

Furnace blower interlock

neutral

class 2

J8-5

 

 

 

 

 

 

M2

BL

J4

 

 

ASSEMBLY

 

A1

 

J11-1

 

 

 

always

 

 

motor

BN

 

 

 

 

J14-1 : NO

 

 

 

 

 

 

 

 

 

 

 

G

 

BK

 

 

 

 

 

 

J14-2 : COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

J14-3 : nc

 

 

 

K2

 

 

J14-3

Furnace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K5

 

 

 

 

 

 

 

 

 

 

 

 

(optional; see notes 3, 5)

 

 

 

K4

 

 

blower

 

 

 

 

 

120 V, 60 Hz W1

 

 

 

 

 

 

 

 

 

 

 

 

J14-1

disconnect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K5

 

 

interlock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(optional; see

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K1

 

 

J14-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

notes 3, 5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

CPU

 

 

J14-4

Override

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J14-5

switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(optional; see

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J14-6

 

 

 

 

 

NOTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

notes 3, 4)

 

 

 

 

 

 

 

 

 

Critical characteristic.

 

 

 

 

 

 

J14-7

 

 

 

 

1. For continued fire protection. Use specified UL listed/CSA

 

 

 

 

 

 

 

Field wiring

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J14-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

 

Certified line fuse.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J14-9

 

 

 

 

2. If any of the original wire, as supplied, must be replaced,

 

COLOR CODE

 

 

 

 

 

 

J14-10

control (see

from

 

 

 

 

use the same equivalent wire.

 

 

 

BK

 

BLACK

 

 

 

 

 

 

 

notes 3, 4)

 

 

 

 

3. Field wiring must comply with applicable codes,

BL

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

BN

 

BROWN

 

 

 

 

 

 

 

 

its

 

 

 

 

ordinances and regulations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

4. Remote controls (class 2 circuit) available,

 

R

 

 

RED

 

 

 

 

 

 

 

 

power

 

 

 

 

see instruction manual.

 

 

 

W

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

5. Furnace fan circuit must be class 2 circuit only.

Y

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

6. To obtain medium speed, interchange

 

 

nc

 

no connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

source.

 

 

 

 

BLUE and RED transformer wires at J9.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VE0130A

 

The medium speed is for special use only.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 20
Image 20
Broan ERV90HCS, HRV90H 6WIRINGDIAGRAM, disconnect, 120V, 60Hz, from, power, ofRiskelectrical shocks. Before, Color Code