Bryant 127A Outdoor Unit Connected to Factory Approved Indoor Unit, Sweat Connection, Minutes

Models: 127A

1 10
Download 10 pages 14.28 Kb
Page 3
Image 3
Outdoor Unit Connected to Factory Approved Indoor Unit

Outdoor Unit Connected to Factory Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for operation with factory approved ARI rated indoor unit when connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1.) Use refrigerant grade tubing

Sweat Connection

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR*

Connection

Connection

Tube

(SERIES)

& Max. Tube

Diameter

Diameter

 

Diameter

 

 

 

24

3/8

3/4

3/4

36

3/8

7/8

7/8

48

3/8

7/8

1---1/8

60

3/8

7/8

1---1/8

*Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.

Notes:

1.Do not apply capillary tube or fixed orifice indoor coils to these units.

2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide line--- Air Conditioners and Heat Pumps using Puron refrigerant.

3.For alternate liquid line options on 18---42 size units, see Product Data or Residential Piping and Application Guideline

Install Liquid-Line Filter Drier Indoor

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

1.Installation of filter drier in liquid line is required.

2.Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1.Braze 5-in. liquid tube to the indoor coil.

2.Wrap filter drier with damp cloth.

3.Braze filter drier to above 5-in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.

4.Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 - Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.

5000

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

4000

 

 

 

 

 

LEAK IN

3500

 

 

 

 

 

 

 

 

 

 

SYSTEM

3000

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

MICRONS2000

 

 

 

 

 

VACUUM TIGHT

1500

 

 

 

 

 

 

 

 

 

 

TOO WET

1000

 

 

 

 

 

 

 

 

 

 

TIGHT

500

 

 

 

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

MINUTES

 

 

 

 

 

 

 

 

 

 

A95424

Fig. 4 - Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

127A

3

Page 3
Image 3
Bryant 127A Outdoor Unit Connected to Factory Approved Indoor Unit, Refrigerant Tubing Connection Outdoor, Minutes