ELECTRICAL DATA

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

UNIT SIZE

V/PH

OPER VOLTS*

COMPR

FAN

MCA

WIRE

WIRE

LENGTH

LENGTH

FUSE**

--- SERIES

 

 

 

 

 

SIZE{

SIZE{

ft (m)}

ft (m)}

or CKT

 

 

 

 

 

 

 

 

 

 

 

 

BRK

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

60° C

75° C

 

 

 

AMPS

018---B

 

 

 

48.0

9.0

0.5

11.7

14

14

67 (20.4)

64 (19.5)

20

024---B

 

 

 

58.3

13.5

0.7

17.5

14

14

45 (13.7)

43 (13.1)

25

030---B

 

 

 

73.0

14.1

0.7

18.3

14

14

43 (13.1)

41 (12.5)

25

036---B

208/230/1

253

187

79.0

16.7

1.1

21.9

12

12

57 (17.4)

54 (16.5)

35

042---B

 

 

 

112.0

17.9

1.3

23.7

10

10

84 (25.6)

80 (24.4)

40

048---B

 

 

 

117.0

21.8

1.3

28.5

10

10

70 (21.3)

67 (20.4)

45

060---B

 

 

 

134.0

26.4

1.3

34.3

8

8

91 (27.7)

86 (26.2)

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Complies with 2001 requirements of ASHRAE Standards 90.1

A-WEIGHTED SOUND POWER (dBA)

UNIT SIZE ---

STANDARD

 

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

 

SERIES

RATING

125

250

500

1000

2000

4000

8000

018---B

67

51.0

58.0

60.5

60.0

59.5

52.5

47.0

024---B

66

55.0

55.5

59.5

61.0

59.0

54.5

47.0

030---B

68

56.0

58.5

63.0

61.0

60.0

52.5

45.0

036---B

70

62.5

62.0

64.5

63.0

60.5

55.5

49.0

042---B

70

61.5

60.5

62.0

63.5

61.0

55.5

51.0

048---B

71

61.5

62.5

63.0

64.0

62.0

57.5

51.5

060---B

73

59.5

63.0

64.0

67.0

63.0

58.0

53.5

NOTE: Tested in accordance with ARI Standard 270

---95. (Not listed with ARI).

 

 

 

 

 

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING _F (_C)

018---B

9

(5.0)

024---B

9

(5.0)

030---B

13 (7.2)

036---B

8

(4.4)

042---B

10 (5.6)

048---B

8

(4.4)

060---B

14 (7.8)

165A

7

Page 7
Image 7
Bryant 165A manual Electrical Data, A-WEIGHTEDSOUND POWER dBA, Charging Subcooling Txv-Typeexpansion Device