OAT Thermistor must be locked in place with spherical nib end facing towards the front of the control box
OCT Thermistor must be secured tight on the liquid tube.
Fig. 8 - Outdoor Air Thermistor (OAT) Attachment | Fig. 9 - Outdoor Coil Thermistor (OCT) Attachment | |||
| ||||
| Table 6 – TROUBLESHOOTING | |||
|
|
|
| |
|
| AMBER |
| |
OPERATION | FAULT | LED | POSSIBLE CAUSE AND ACTION | |
FLASH | ||||
|
|
| ||
|
| CODE |
| |
Standby – no call for unit op- |
| On sol- |
| |
None | id, no | Normal operation | ||
eration | ||||
| flash |
| ||
|
|
| ||
None | 1, pause | Normal operation | ||
tion | ||||
|
|
| ||
None | 2, pause | Normal operation | ||
tion | ||||
|
|
| ||
| System Communications | 16 | Communication with user interface lost. Check wiring to User Interface, indoor | |
| Failure | and outdoor units | ||
|
| |||
| Invalid Model Plug | 25 | Control does not detect a model plug or detects an invalid model plug. Unit | |
| will not operate without correct model plug. | |||
|
|
| ||
| High Pressure Switch Open | 31* | ||
| and coils for airflow restrictions. | |||
|
|
| ||
| Low Pressure Switch Open | 32* | Low pressure switch trip. Check refrigerant charge and indoor air flow | |
| Control Fault | 45 | Outdoor unit control board has failed. Control board needs to be replaced. | |
| Brown Out (230 v) | 46 | Line voltage < 187v for at least 4 seconds. Compressor and fan operation not | |
| allowed until voltage>190v. Verify line voltage. | |||
|
|
| ||
|
|
| There is no 230v at the contactor when indoor unit is powered and cooling/ | |
| No 230v at Unit | 47 | heating demand exists. Verify the disconnect is closed and 230v wiring is | |
|
|
| connected to the unit. | |
| Outdoor Air Temp Sensor | 53 | Outdoor air sensor not reading or out of range. Ohm out sensor and check | |
| Fault | wiring. | ||
|
| |||
| Outdoor Coil Sensor Fault | 55 | Coil sensor not reading or out of range. Ohm out sensor and check wiring. | |
| Thermistors out of range | 56 | Improper relationship between coil sensor and outdoor air sensor. Ohm out | |
| sensors and check wiring. | |||
|
|
| ||
|
|
| Compressor operation detected then disappears while | |
| Low stage Thermal Cutout | 71* | exists. Possible causes are internal compressor overload trip or start relay and | |
|
|
| capacitor held in circuit too long(if installed) | |
|
|
| Compressor operation detected then disappears while | |
| High stage Thermal Cutout | 72* | exists. Possible causes are internal compressor overload trip or start relay and | |
|
|
| capacitor held in circuit too long (if installed) | |
| Contactor Shorted | 73 | Compressor voltage sensed when no demand for compressor operation | |
| exists. Contactor may be stuck closed or there is a wiring error. | |||
|
|
| ||
| No 230V at Compressor | 74 | Compressor voltage not sensed when compressor should be starting. Contac- | |
| tor may be stuck open or there is a wiring error. | |||
|
|
| ||
| 81 | Thermal cutout occurs in three consecutive low/ | ||
| ||||
|
|
| ||
| 82 | Thermal cutout occurs in three consecutive | ||
| out | |||
|
| |||
| Low Pressure Lockout | 83 | Low pressure switch trip has occurred during 3 consecutive cycles. Unit oper- | |
| ation locked out for 4 hours or until 24v power recycled. | |||
|
|
| ||
| High Pressure Lockout | 84 | High pressure switch trip has occurred during 3 consecutive cycles. Unit oper- | |
| ation locked out for 4 hours or until 24v power recycled. | |||
|
|
| ||
* Sequence: Compressor contactor is |
187B / 180B
11