Bryant 187B 180B, Refrigerant Tubing Connection Outdoor, Sweat Connection, Accessory Usage

Models: 187B

1 14
Download 14 pages 56.82 Kb
Page 3
Image 3
Table 1 – Accessory Usage

Table 1 – Accessory Usage

 

REQUIRED FOR

 

REQUIRED FOR SEA COAST

 

LOW---AMBIENT COOLING

REQUIRED FOR LONG LINE

ACCESSORY

APPLICATIONS

APPLICATIONS

APPLICATIONS*

 

(Within 2 miles/3.22 km)

 

(Below 55°F/12.8_C)

 

 

 

 

Compressor Start Assist Kit

No

Yes

No

Crankcase Heater

Standard

Standard

Standard

 

Standard with Evolutiont Control

 

 

Evaporator Freeze Protection

(Low Ambient not allowed with

No

No

 

non ---communicating thermostat)

 

 

Liquid---Line Solenoid Valve

No

No

No

 

Standard with Evolution Control

 

 

Low---Ambient Control

(Low ambient not allowed with

No

No

 

non ---communicating thermostat)

 

 

Puron Refrigerant Balance Port Hard---

Yes{

Yes{

Yes{

ShutOff TXV

 

 

 

Support Feet

Recommended

No

Recommended

 

Standard with Evolution Control

 

 

Winter Start Control

(Low Ambient not allowed with

No

No

 

non ---communicating thermostat)

 

 

*For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent length), refer to the Long Line Guideline—Air Conditioners and Heat Pumps using Puron® Refrigerant.

{Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.

/ 180B

Outdoor Unit Connected to Factory Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

NOTE: If the indoor furnace coil width is more than the furnace casing width, refer to the indoor coil Installation Instructions for transition requirements.

!WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury or equipment damage.

PuronR refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on PuronR refrigerant equipment.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 2.) Use refrigerant grade tubing.

Sweat Connection

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

Table 2 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

 

LIQUID

RATED VAPOR*

UNIT SIZE

Connection

Connection

Tube

 

& Max. Tube

Diameter

Diameter

 

Diameter

 

 

 

024

3/8

3/4

3/4

036

3/8

7/8

7/8

048

3/8

7/8

1-1/8

060

3/8

7/8

1-1/8

*Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.

Notes:

1.Do not apply capillary tube or fixed orifice indoor coils to these units.

2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide line--- Air Conditioners and Heat Pumps using Puron refrigerant.

3.For alternate liquid line options on 18---42 size units, see Product Data or Residential Piping and Application Guideline

Install Liquid-Line Filter Drier Indoor

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

1.Installation of filter drier in liquid line is required.

2.Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.

187B

3

Page 3
Image 3
Bryant 187B 180B, Refrigerant Tubing Connection Outdoor, Sweat Connection, Install Liquid-LineFilter Drier Indoor