Table 1 – Accessory Usage
| REQUIRED FOR |
| REQUIRED FOR SEA COAST | |
| REQUIRED FOR LONG LINE | |||
ACCESSORY | APPLICATIONS | |||
APPLICATIONS | APPLICATIONS* | |||
| (Within 2 miles/3.22 km) | |||
| (Below 55°F/12.8_C) |
| ||
|
|
| ||
Compressor Start Assist Kit | No | Yes | No | |
Crankcase Heater | Standard | Standard | Standard | |
| Standard with Evolutiont Control |
|
| |
Evaporator Freeze Protection | (Low Ambient not allowed with | No | No | |
| non |
|
| |
No | No | No | ||
| Standard with Evolution Control |
|
| |
(Low ambient not allowed with | No | No | ||
| non |
|
| |
Puron Refrigerant Balance Port | Yes{ | Yes{ | Yes{ | |
ShutOff TXV | ||||
|
|
| ||
Support Feet | Recommended | No | Recommended | |
| Standard with Evolution Control |
|
| |
Winter Start Control | (Low Ambient not allowed with | No | No | |
| non |
|
|
*For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent length), refer to the Long Line
{Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
/ 180B
Outdoor Unit Connected to Factory Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
NOTE: If the indoor furnace coil width is more than the furnace casing width, refer to the indoor coil Installation Instructions for transition requirements.
!WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
PuronR refrigerant systems operate at higher pressures than standard
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 2.) Use refrigerant grade tubing.
Sweat Connection
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a
Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
Table 2 – Refrigerant Connections and Recommended Liquid
and Vapor Tube Diameters (In.)
| LIQUID | RATED VAPOR* | |
UNIT SIZE | Connection | Connection | Tube |
| & Max. Tube | Diameter | Diameter |
| Diameter | ||
|
|
| |
024 | 3/8 | 3/4 | 3/4 |
036 | 3/8 | 7/8 | 7/8 |
048 | 3/8 | 7/8 | |
060 | 3/8 | 7/8 |
*Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.
Notes:
1.Do not apply capillary tube or fixed orifice indoor coils to these units.
2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide
3.For alternate liquid line options on
Install Liquid-Line Filter Drier Indoor
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
1.Installation of filter drier in liquid line is required.
2.Filter drier must be wrapped in a
187B
3