Refer to Fig. 3 and install filter drier as follows:

1.Braze 5-in. liquid tube to the indoor coil.

2.Wrap filter drier with damp cloth.

3.Braze filter drier to above 5-in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.

4.Connect and braze liquid refrigerant tube to the filter drier.

 

 

 

A05178

 

 

 

Fig. 3 - Liquid Line Filter Drier

 

 

 

/ 180B

 

Evacuate Refrigerant Tubing and Indoor Coil

 

 

 

!

CAUTION

187B

 

UNIT DAMAGE HAZARD

 

 

 

 

Failure to follow this caution may result in equipment

 

 

damage or improper operation.

 

 

 

 

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.

accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.

 

5000

 

 

4500

 

 

4000

LEAK IN

MICRONS

3500

SYSTEM

3000

 

2500

 

 

 

DISCONNECT

PER N. E. C. AND/OR LOCAL CODES

FIELD POWER

WIRING

FIELD GROUND

WIRING

CONTACTOR

GROUND

LUG

A91056

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VACUUM TIGHT

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOO WET

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIGHT

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

MINUTES

 

 

 

 

 

 

 

 

 

 

A95424

Fig. 4 - Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Fig. 5 - Line Connections

Connect Control Wiring

This unit is capable of communication with an Evolution Control, or will operate using standard 24v 2-stage thermostat. Route 24-v control wires through control wiring grommet and connect leads to control board. When an Evolution User Interface is available, connect A, B, C and D connections only. If a 2-stage thermostat is used, connect to the R, C, Y1, and Y2 connections. Refer to the wiring label to further clarification.

Use No. 18 AWG color-coded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.

NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.

4

Page 4
Image 4
Bryant 187B installation instructions Make Electrical Connections

187B specifications

The Bryant 187B is a cutting-edge heating and cooling solution designed for efficiency and performance in residential and light commercial applications. This HVAC unit incorporates advanced technologies that prioritize energy savings, user comfort, and reliability.

One of the primary features of the Bryant 187B is its two-stage cooling and heating capability. This technology allows the system to operate at lower capacity most of the time, which not only saves energy but also enhances indoor comfort by minimizing temperature fluctuations. When the demand increases, the system automatically ramps up to meet the needs, providing a consistent and comfortable environment.

Efficiency is a hallmark of the Bryant 187B, boasting a SEER rating of up to 18.5 and an AFUE rating of 80%. These ratings signify that the unit exceeds minimum efficiency requirements, leading to lower energy bills and a reduced carbon footprint. The inclusion of environmentally friendly refrigerants, such as R-410A, further emphasizes its commitment to sustainable practices.

Another notable characteristic of the Bryant 187B is its Quiet Operation technology. The unit is designed with sound-dampening features that reduce operational noise, ensuring that the indoor environment remains peaceful. This is particularly valuable in residential areas where noise pollution can be a concern.

The Bryant 187B also comes equipped with advanced thermostat compatibility, allowing homeowners to integrate smart home technologies seamlessly. This feature enables remote temperature control and scheduling, leading to more efficient energy use and enhanced comfort. Users can easily adjust settings through mobile applications, ensuring that their home is always at the desired temperature upon arrival.

Reliability is a key aspect of the Bryant 187B, featuring a robust construction designed to withstand various environmental conditions. With a durable cabinet and high-quality components, this unit is built to last and requires minimal maintenance.

Overall, the Bryant 187B exemplifies modern HVAC technology, combining efficiency, comfort, and reliability into a single cohesive system. It remains an excellent choice for those seeking an effective solution for heating and cooling needs, ensuring that homes remain comfortable throughout the year while being mindful of energy consumption.