DETAILED COOLING CAPACITIES#

EVAPORATOR AIR

 

 

 

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES ° F (° C)

 

 

 

 

 

 

 

 

 

 

75 (23.9)

 

 

85 (29.4)

 

 

95 (35)

 

 

105 (40.6)

 

 

 

115 (46.1)

 

 

125 (51.7)

 

CFM

EWB

Capacity MBtuh

Total

Capacity MBtuh

Total

Capacity MBtuh

Total

Capacity MBtuh

 

Total

Capacity MBtuh

Total

Capacity MBtuh

Total

 

 

System

 

 

System

 

 

 

System

 

 

 

System

 

 

System

 

 

System

° F (° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

Sens‡

KW**

Total

Sens‡

KW**

Total

 

Sens‡

KW**

Total

Sens‡

 

KW**

Total

Sens‡

KW**

Total

Sens‡

KW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

213ANA060---D Outdoor Section With FY4ANB060 Indoor Section

72 (22.2)

70.34

35.38

4.52

67.10

34.14

4.98

63.63

32.83

5.48

60.01

31.48

6.03

56.06

30.03

6.63

51.70

28.45

7.27

 

67 (19.4)

64.72

44.25

4.46

61.72

42.98

4.92

58.50

41.62

5.42

55.15

40.23

5.97

51.50

38.73

6.57

47.50

37.11

7.21

1750

63 (17.2)††

60.52

42.98

4.41

57.68

41.67

4.87

54.66

40.31

5.37

51.50

38.90

5.92

48.09

37.40

6.52

44.37

35.78

7.17

 

62 (16.7)

59.39

53.03

4.40

56.60

51.67

4.86

53.67

50.23

5.36

50.63

48.68

5.91

47.46

47.46

6.51

44.40

44.40

7.17

 

57 (13.9)

57.36

57.36

4.38

55.12

55.12

4.84

52.73

52.73

5.35

50.21

50.21

5.90

47.45

47.45

6.51

44.40

44.40

7.17

 

72 (22.2)

71.28

36.87

4.64

67.97

35.64

5.09

64.37

34.31

5.59

60.64

32.95

6.14

56.56

31.48

6.74

52.07

29.88

7.39

 

67 (19.4)

65.71

46.88

4.58

62.60

45.59

5.03

59.26

44.22

5.53

55.79

42.80

6.08

52.01

41.28

6.69

47.89

39.62

7.33

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63 (17.2)††

61.54

45.45

4.53

58.58

44.14

4.99

55.44

42.75

5.49

52.17

41.32

6.04

48.63

39.78

6.64

44.80

38.11

7.28

 

62 (16.7)

60.48

56.64

4.52

57.63

55.18

4.98

54.66

54.31

5.48

51.85

51.85

6.03

48.91

48.91

6.64

45.66

45.66

7.30

 

57 (13.9)

59.46

59.46

4.51

57.07

57.07

4.97

54.53

54.53

5.48

51.85

51.85

6.03

48.92

48.92

6.64

45.67

45.67

7.30

 

72 (22.2)

71.96

38.30

4.75

68.56

37.06

5.21

64.87

35.72

5.71

61.04

34.35

6.26

56.86

32.87

6.86

52.26

31.26

7.50

 

67 (19.4)

66.40

49.38

4.70

63.21

48.09

5.15

59.77

46.69

5.65

56.21

45.25

6.20

52.34

43.69

6.80

48.13

41.98

7.44

2250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63 (17.2)††

62.26

47.81

4.65

59.21

46.48

5.10

55.98

45.06

5.60

52.62

43.60

6.15

49.00

42.02

6.75

45.07

40.30

7.40

 

62 (16.7)

61.41

59.80

4.64

58.65

58.65

5.10

55.97

55.97

5.61

53.15

53.15

6.16

50.06

50.06

6.77

46.64

46.64

7.42

 

57 (13.9)

61.16

61.16

4.64

58.65

58.65

5.10

55.97

55.97

5.61

53.16

53.16

6.16

50.07

50.07

6.77

46.65

46.65

7.42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING INDOOR

CAPACITY

POWER

FURNACE MODEL

 

COOLING INDOOR

CAPACITY

POWER

FURNACE MODEL

 

COOLING INDOOR

CAPACITY

POWER

FURNACE MODEL

 

MODEL

 

MODEL

 

MODEL

 

 

 

 

 

 

 

 

 

 

 

 

 

*FY4ANB060

1.00

1.00

 

 

CSPH*6012A**

1.00

0.96

315(A,J)AV066135

 

CSPH*6012A**

0.99

0.99

355(A,C)AV060100

 

FE4ANB006

1.02

0.98

 

 

CAP**6024A**

1.00

0.96

315(A,J)AV066155

 

CAP**6024A**

0.98

0.98

355(A,C)AV060120

 

FV4BNB006

1.02

0.96

 

 

CNPH*6024A**

0.99

0.96

315(A,J)AV066155

 

CNPH*6024A**

0.98

0.98

355(A,C)AV060120

 

FX4CN(B,F)060

1.01

0.97

 

 

CNPV*6024A**

0.99

0.96

315(A,J)AV066155

 

CNPV*6024A**

0.98

0.98

355(A,C)AV060120

 

CAP**6021A**

0.99

0.99

 

 

CSPH*6012A**

1.00

0.96

315(A,J)AV066155

 

CSPH*6012A**

0.99

0.99

355(A,C)AV060120

 

CAP**6024A**

0.99

0.99

 

 

CNPH*6024A**

0.98

1.01

353AAV048080

 

CAP**6021A**

0.99

0.97

313*AV048090

 

CNPH*6024A**

0.99

0.99

 

 

CSPH*6012A**

0.98

1.01

353AAV048080

 

CNPH*6024A**

0.98

0.97

313*AV048090

33

CNPV*6024A**

0.99

0.99

 

 

CAP**6021A**

0.99

0.97

353AAV060100

 

CSPH*6012A**

0.99

0.97

313*AV048090

 

CSPH*6012A**

1.00

1.00

 

 

CNPH*6024A**

0.99

0.97

353AAV060100

 

CAP**6021A**

1.00

0.98

313*AV060110

 

CAP**6021A**

0.99

0.97

315(A,J)AV060110

 

CSPH*6012A**

0.99

0.97

353AAV060100

 

CNPH*6024A**

0.99

0.97

313*AV060110

 

CNPH*6024A**

0.99

0.97

315(A,J)AV060110

 

CAP**6024A**

0.99

0.97

353AAV060120

 

CSPH*6012A**

1.00

0.98

313*AV060110

 

CSPH*6012A**

1.00

0.98

315(A,J)AV060110

 

CNPH*6024A**

0.99

0.97

353AAV060120

 

CAP**6024A**

0.99

0.97

313*AV060135

 

CAP**6024A**

0.99

0.97

315(A,J)AV066135

 

CNPV*6024A**

0.99

0.97

353AAV060120

 

CNPH*6024A**

0.99

0.97

313*AV060135

 

CNPH*6024A**

0.99

0.97

315(A,J)AV066135

 

CSPH*6012A**

1.00

0.98

353AAV060120

 

CNPV*6024A**

0.99

0.97

313*AV060135

 

CNPV*6024A**

0.99

0.97

315(A,J)AV066135

 

CAP**6021A**

0.98

0.98

355(A,C)AV060100

 

CSPH*6012A**

1.00

0.98

313*AV060135

* Tested combination.

{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).

#Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

** System kw is total of indoor and outdoor unit kilowatts.

{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.

NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EWB — Entering Wet Bulb

213A

Page 33
Image 33
Bryant warranty 213ANA060---D Outdoor Section With FY4ANB060 Indoor Section

213A specifications

The Bryant 213A is a cutting-edge system known for its impressive performance and reliability in heating and cooling applications. Designed for residential and light commercial use, it stands out due to its efficiency and innovative features, making it a popular choice among homeowners and contractors alike.

One of the main features of the Bryant 213A is its advanced two-stage cooling and heating capability. This allows for more precise temperature control and enhanced comfort. By adjusting its output based on the current demand, the unit operates at lower speeds during moderate conditions, which helps in saving energy while still maintaining desired comfort levels.

Efficiency is another hallmark of the Bryant 213A. It boasts a high Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER), making it one of the most energy-efficient systems in the market. This efficiency not only contributes to lower energy bills but also helps in reducing the environmental footprint of the home, making it a greener choice for those conscious of their energy consumption.

The 213A leverages state-of-the-art technology such as a variable-speed compressor and advanced refrigerant management. This technology facilitates smooth operation and minimizes temperature fluctuations. Additionally, the unit is designed for quiet operation, which means it can efficiently cool or heat a home without intrusive noise, resulting in a more comfortable living environment.

Installation flexibility is another significant advantage of the Bryant 213A. The system is compatible with various ductwork configurations and can be easily integrated into existing HVAC systems. This adaptability makes it suitable for different home sizes and layouts, providing solutions for both new constructions and retrofits.

Durability is a core characteristic of the Bryant 213A. Crafted with high-quality materials and backed by a robust warranty, it ensures longevity and dependable performance. The unit is built to withstand various weather conditions and is designed with low maintenance in mind, further enhancing its appeal.

In conclusion, the Bryant 213A combines efficiency, advanced technology, and durability, making it an exceptional choice for heating and cooling needs. Its innovative features, quiet operation, and adaptability to different home environments set it apart in the HVAC landscape. Selecting the Bryant 213A ensures a comfortable, energy-efficient, and reliable climate control solution for any modern home.