ELECTRICAL DATA

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

 

 

 

 

 

 

 

 

FUSE**

UNIT SIZE ---

 

OPER VOLTS*

COMPR

FAN

 

WIRE

WIRE

LENGTH

LENGTH

V/PH

MCA

or CKT

SERIES

 

 

 

 

 

SIZE†

SIZE†

ft (m)‡

ft (m)‡

 

 

 

 

 

 

 

BRK

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

60° C

75° C

AMPS

018---E

 

 

 

48.0

9.0

0.8

12.0

14

14

66 (20.1)

62 (18.9)

20

024---C

 

 

 

58.3

12.8

0.75

16.8

14

14

47 (14.3)

45 (13.7)

25

030---D

 

 

 

77.0

16.0

0.8

20.8

12

12

58 (17.7)

56 (17.1)

30

036---D

208/230/1

253

197

79.0

16.7

0.9

21.7

12

12

58 (17.7)

55 (16.8)

35

042---C

 

 

 

109.0

19.9

1.2

26.0

10

10

77 (23.5)

73 (22.3)

40

048---D

 

 

 

117.0

21.8

1.2

28.4

8

8

109 (33.2)

104 (31.7)

50

060---D

 

 

 

134.0

26.3

1.2

34.1

8

8

91 (27.7)

87 (26.5)

50

*Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),

trade name ROMEX, shall be that of 60_C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA ---Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Complies with 2001 requirements of ASHRAE Standards 90.1

A-WEIGHTED SOUND POWER

 

STANDARD

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

UNIT SIZE --- SERIES

RATING

 

 

 

 

 

 

 

125

250

500

1000

2000

4000

8000

 

(dBA)

018---E

74

52.0

63.5

68.0

70.5

66.5

62.0

57.5

024---C

75

54.5

64.0

69.0

69.5

67.5

64.0

58.0

030---D

74

52.0

62.5

66.5

68.5

65.0

63.5

59.0

036---D

72

55.0

62.0

63.5

66.0

64.0

61.5

54.0

042---C

77

55.5

60.0

63.5

71.5

65.0

62.5

59.0

048---D

77

58.0

65.5

68.5

72.0

66.5

60.5

53.0

060---D

77

55.0

63.0

67.5

71.5

68.0

64.0

60.5

NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).

A-WEIGHTED SOUND POWER WITH SOUND HOOD

 

STANDARD

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

UNIT SIZE --- SERIES

RATING

 

 

 

 

 

 

 

 

(dBA)

125

250

500

1000

2000

4000

8000

018---E

73

52.5

63.0

67.5

69.0

66.0

62.0

55.5

024---C

74

54.0

63.5

69.0

69.0

67.5

63.5

57.5

030---D

74

51.5

62.0

66.5

67.5

64.5

62.0

57.5

036---D

70

54.5

62.0

63.5

64.5

63.0

60.0

51.5

042---C

75

55.0

60.5

63.5

69.0

64.5

61.5

56.0

048---D

74

58.0

64.5

69.0

68.5

66.0

60.0

53.0

060---D

74

55.0

63.5

67.0

69.0

66.5

62.0

57.0

NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING ° F (° C)

018---E

10 (5.6)

024---C

12 (6.7)

030---D

12 (6.7)

036---D

9 (5.0)

042---C

11 (6.1)

048---D

11 (6.1)

060---D

12 (6.7)

213A

7

Page 7
Image 7
Bryant 213A Electrical Data, A-Weightedsound Power With Sound Hood, Charging Subcooling Txv-Typeexpansion Device