Bryant 312AAV/JAV instruction manual Venting Notes For Fig

Models: 312AAV/JAV

1 56
Download 56 pages 13.07 Kb
Page 32
Image 32
VENTING NOTES FOR FIG. 35 - 47

312AAV

SEE NOTES: 1,2,4,5,7,8,9

A02068

Fig. 47 - Horizontal Right Application-Vent Elbow Left

VENTING NOTES FOR FIG. 35 - 47

1.For common vent, vent connector sizing and vent material: United States-use the NFGC.

2.Immediately increase to 5-in. or 6-in. (127 or 152 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connector is required, refer to Note 1 above.

3.Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when factory-approved Downflow Vent Guard Kit, is used in the downflow position. See Table 18 for accessory listing.

4.Type-B vent where required, refer to Note 1 above.

5.Four-in. (102 mm) single-wall (26 ga. min.) vent must be used inside furnace casing and when the factory-approved Downflow Vent Guard Kit is used external to the furnace. See Table 18 for accessory listing.

6.Accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration. See Table 18 for accessory listing.

7.Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete application details. See Table 18 for accessory listing.

8.Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, spaced approximately 180_ apart.

9.Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type-B vent connectors per vent connector manufacturer’s recommendations.

10.The total height of the vent and connector shall be at least seven feet (2 M) for the 154,000 Btuh gas input rate model when installed in a downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 40.)

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code

FURNACE

VENT

FURNACE

MINIMUM VENT

MINIMUM VERTICAL

DIAMETER

VENT HEIGHT

ORIENTATION

ORIENTATION

INPUT(BTUH/HR)

IN. (mm)*

FT. (M)**

 

 

 

 

 

 

 

 

 

Vent elbow left, then

154,000

 

 

Downflow

132,000

5 (127)

12 (3.6)

up Fig. 39

 

110,000 (036/--- 12 only)

 

 

 

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right,

154,000

5 (127)

7 (.65)

then up Fig. 42

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent Elbow up Fig.

154,000

5 (127)

7 (.65)

43

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right Fig.

154,000

5 (127)

7 (.65)

44

 

 

 

 

 

 

 

 

 

Downflow

Vent elbow up then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

left Fig. 37

 

 

 

 

Downflow

Vent elbow up, then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

right Fig. 40

 

 

 

 

*4 in. (102 mm) inside casing or vent guard **Including 4 in. (102 mm) vent section(s)

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.

32

Page 32
Image 32
Bryant 312AAV/JAV instruction manual Venting Notes For Fig