312AAV

7

See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17 on the page following these figures

A03182

Fig. 30 - Dual Fuel Thermostat with Two-Stage Furnace

and Two-Speed Heat Pump

See notes 2, 11, and 12 on the page following these figures

A03183

Fig. 31 - Two-Stage Thermostat with Two-Stage Furnace

and Two-Speed Air Conditioner

See notes 1 and 2 on the page following these figures

A03184

Fig. 32 - Single-Stage Thermostat with Two-Stage Furnace and Two-Speed Air Conditioner

FOR FIGURES 26-32

1.Heat pump MUST have a high pressure switch for dual fuel applications.

2.Refer to outdoor equipment Installation Instructions for additional information and setup procedure.

3.Outdoor Air Temperature Sensor must be attached in all dual fuel applications.

4.Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.

5.Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.

6.Dip switch No. 2 on Thermidistat should be set in OFF position for single---speed compressor operation. This is factory default.

7.Dip switch No. 2 on Thermidistat should be set in ON position for two---speed compressor operation.

8.Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.

9.NO connection should be made to the furnace HUM terminal when using a Thermidistat.

10.Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control furnace staging.

11.Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.

12.When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high ---stage heating operation via furnace control algorithm.

13.The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.

14.DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two---speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.

15.Dip switch D on Dual Fuel Thermostat should be set in OFF position for single---speed compressor operation. This is factory default.

16.Dip switch D on Dual Fuel Thermostat should be set in ON position for two---speed compressor operation.

24

Page 24
Image 24
Bryant 312AAV/JAV instruction manual For Figures

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.