Table 14- Orifice Size* And Manifold Pressure (In. wc) For Gas Input Rate (CONT)

313A

A08221A

SERVICE

If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After

status code recall is completed component test will occur. LED CODE

STATUS

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.

CONTINUOUS ON - Control has 24VAC power.

RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

11NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On

RED LED boards stored status codes can also be erased when power (115 VAC or 24 VAC) to control is interrupted.

12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens during blower on-delay.

13LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or

blocked vent switch (if used) is open longer than 3 minutes. - Control will auto reset after three hours. - Refer to #33.

14IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.

21GAS HEATING LOCKOUT - Control will NOT auto reset.

Check for: - Mis-wired gas valve

-Defective control (valve relay)

22ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de- energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve - Stuck-open gas valve

23PRESSURE SWITCH DID NOT OPEN Check for:

- Obstructed pressure tubing.

- Pressure switch stuck closed.

24SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring.

COMPONENT TEST

To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.

327596-101 REV. B

31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,

inducer shuts off for 15 minutes before retry. Check for: - Excessive wind

- Proper vent sizing

- Defective inducer motor

- Low inducer voltage (115VAC)

- Defective pressure switch

- Inadequate combustion air supply

- Disconnected or obstructed pressure tubing

- Low inlet gas pressure (if LGPS used)

- Restricted vent

If it opens during blower on-delay period, blower will come on for the selected blower off-delay.

33LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13.

If open less than 3 minutes status code #33 continues to flash until blower shuts off.

Flame rollout switch and BVSS require manual reset. Check for:

- Restricted vent

- Proper vent sizing

- Loose blower wheel.

- Excessive wind

-Dirty filter or restricted duct system.

-Defective blower motor or capacitor. - Defective switch or connections.

-Inadequate combustion air supply (Flame Roll-out Switch open).

34IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Flame sensor must not be grounded

-Oxide buildup on flame sensor (clean with fine steel wool).

-Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

- Gas valve defective or gas valve turned off - Manual valve shut-off

- Defective Hot Surface Ignitor

- Control ground continuity

 

- Low inlet gas pressure

- Inadequate flame carryover or rough ignition

- Green/Yellow wire MUST be connected to furnace sheet metal

 

45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour

lockout due to;

- Gas valve relay stuck open

- Flame sense circuit failure

- Software check error

Reset power to clear lockout.

Replace control if status code repeats.

A04223

Fig. 55 - Service Label

45

Page 45
Image 45
Bryant 313AAV instruction manual Service

313AAV specifications

The Bryant 313AAV is a state-of-the-art air conditioning unit renowned for its reliable performance and energy-efficient design. Crafted for residential use, this model provides optimal cooling while ensuring low operational costs. Its standout feature is the variable-speed compressor, which adjusts its output based on the cooling needs of your home. This not only leads to more consistent temperatures but also enhances energy efficiency, allowing homeowners to save on their utility bills.

One of the key technologies employed in the Bryant 313AAV is the Infinity Control system. This smart thermostat allows users to manage their home's temperature remotely via a smartphone app. The system is compatible with Wi-Fi, enabling seamless connectivity and ease of use. Additionally, the unit's advanced communication technology enables it to monitor system performance and send alerts for maintenance, ensuring that the air conditioning system operates at its best.

The Bryant 313AAV is designed with sound reduction technology, which minimizes operational noise, making it an excellent choice for residential environments where peace and quiet are a priority. Its cabinet is constructed for durability and features enhanced insulation to further reduce noise levels.

Another impressive characteristic of the Bryant 313AAV is its SEER rating. With Seasonal Energy Efficiency Ratio (SEER) ratings of up to 20, this model exceeds the minimum efficiency standards set by the U.S. government, making it an environmentally friendly option. This high SEER rating means that the unit consumes less energy while providing superior cooling performance.

Installation is made straightforward thanks to the unit's compact size and flexible design. Additionally, the Bryant 313AAV is equipped with EcoWise refrigerant, which is designed to be more environmentally responsible while ensuring efficient cooling performance.

In summary, the Bryant 313AAV air conditioning unit stands out due to its energy efficiency, advanced technology features, and quiet operation. It is an ideal choice for homeowners looking to enhance their comfort while keeping energy costs in check. With its reliable performance and innovative characteristics, the Bryant 313AAV is well-equipped to meet the cooling demands of today's households.