Bryant 331JAV, 330JAV Start, Troubleshooting Guide, Electrical Shock Hazard, A97544, Code

Models: 330JAV 331JAV

1 12
Download 12 pages 20.11 Kb
Page 10
Image 10
NOTES:

NOTES:

1.Refer to information label on blower compartment door for procedure for use of LED status codes and problem solving suggestions.

2.LED indicator is viewed through window in blower compartment door.

3.If 115-vac power is de-energized or interrupted during a call for heat, the indoor blower will run for 90 sec before a gas heating cycle begins – Code 12.

4.After replacing any component, verify correct operating sequence.

START

Turn thermostat OFF.

On furnace control, note current

settings for setup switches 1 (SW-1) and 2 (SW-2) then set SW-1 to OFF and SW-2 to ON.

Cycle 115-v power

 

off for 3 sec, then on.

 

Continuous LED?

No

 

Yes

 

Set thermostat to call for heat.

 

Set FAN to AUTO mode.

 

Draft inducer motor starts.

No

 

Yes

No

Is Code 22 displayed?

 

Yes

 

Flame present when not normal.

 

Replace gas valve.

 

15-sec inducer pre-purge.

 

Yes

 

Ignitor warms up and glows

No

 

orange/yellow; 17-sec warm-up.

 

Yes

 

Main burners ignite.

No

 

Yes

 

Main burners stay on.

No

 

Yes

 

Indoor blower motor starts on

No

 

heating speed after 45-sec

 

 

 

 

warm-up period.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

No

 

 

 

 

Furnace runs until call for

 

 

 

 

heat ends.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Turn thermostat to OFF; gas valve

No

 

shuts off burners; 5-sec inducer

 

 

 

post purge.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

No

 

Indoor blower motor stops after

 

90, 135, 180, or 225 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

Heating sequence of operation complete. Remove blower door, move setup switch 1 (SW-1) to ON

TROUBLESHOOTING

GUIDE

START If LED is flashing rapidly, check line voltage polarity.

TROUBLESHOOTING If Code 24 is displayed, check for blown fuse.

Code 43. If LED is OFF, check line voltage and 24-v transformer.

ELECTRICAL SHOCK HAZARD If Code 45 is displayed, replace control.

Is indoor blower on ?

ONLY QUALIFIED AND TRAINED No

SERVICE PERSONNEL SHOULD 24v should be present across Com and W at furnace control. If not, check for:

1.Open thermostat.

2.Open 24-v fuse (FU1) – Code 24.

3.Failed transformer.

FAN to AUTO mode. If Code 23 is displayed, the pressure switch(es) is stuck closed. Replace switch and/or check pressure tube for blockage.

A97544 System malfunction – Code 21.

Manual background 115v should be present at the inducer motor. If so, replace inducer motor. If not, check 115-v wiring.

Manual background If Code 32 is displayed check for:

1.Open gas inlet pressure switch (when used).

2.Open pressure switch (LPS) and/or tube – Code 32.

3.Open draft safeguard switch (DSS) – Code 32.

4.Open auxiliary switch (ALS)(downflow only) – Code 32.

5.Check all low-voltage wiring connections.

Manual background 115v should be present at the ignitor. If so, replace the ignitor; if not, check 115-vac wiring to ignitor.

Manual background LPS, DSS, or ALS open while HPS if closed (high-gas-heat only) –

Code 43.

Control will attempt to light burners 4 times (approximately 1 minute between attempts – Code 34). Voltage is present at the gas valve for 7 sec during each ignition trial. System will lockout after 4 attempts.

Manual background Is the gas valve control knob or switch in the OPEN or ON position? Manual background 24v should be present across the gas valve terminals C and M/P (and C and HI for high-stage gas test) during the 7 sec ignition trial. If not, check all low-voltage wiring connections to valve.

Manual background If 24v are present, and main gas does not flow:

1.Supply pressure between 4.5- and 13.6-in. wc. If not, adjust supply pressure.

2.If supply pressure is between 4.5- and 13.6-in. wc, replace gas valve.

Manual background Check ignitor position.

Manual background Check burner carryover gap.

Manual background Check gas supply pressure (4.5-in. wc minimum).

Manual background Check manifold pressure (1.3- to 1.7-in. wc for low-stage gas; 3.2- to 3.8-in. wc for high-stage gas).

Manual background Check for proper orifice size.

Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check code information label to diagnose.

Manual background Check polarity of 115-v power at J-box and control. Twinned furnace polarities must match – rapid flashing LED.

Manual background Check ground continutity from J-box to control.

Manual background Check flame sensor microamps (4.0 nominal; 0.5 minimum for control to recognize flame).

Manual background 115v should be present at the blower motor. If so, check capacitor. If capacitor is OK, replace blower motor. If 115v are not present at the blower motor, check all 115-v wiring to motor.

Manual background If not, check for:

1.Satisfied thermostat.

2.Open inlet gas pressure switch (when used).

3.Open pressure switch (LPS) – Code 32.

4.Open draft safeguard switch (DSS) – Code 32.

5.Open auxilliary limit (ALS)(downflow only) – Code 32.

6.Open 24-v fuse (FU1) – Code 24.

7.Open limit switch (LS) – Code 13 or 33.

8.Open flame rollout switch (FRS) – Code 13 or 33.

9.Check 115-v line voltage – LED off.

Check for sources of electrical noise interference (electronic air cleaners, nearby TV, or radio antennas).

Manual background If inducer and burners continue to operate, check for 24v at the gas valve. If 24v are present, verify that the thermostat is open across R and W. If no voltage is present, turn the gas valve control knob or switch to the OFF position. Replace gas valve.

!WARNING

ELECTRICAL SHOCK HAZARD

ONLY QUALIFIED AND TRAINED

SERVICE PERSONNEL SHOULD

PERFORM THIS PROCEDURE

 

 

24v should be present across R

 

Yes

and Com. If not, check for:

 

 

1. Open flame rollout switch

 

 

 

 

(FRS) – Code 33.

 

 

2.Open limit switch (LS) –

Code 33.

3.Check all low-voltage wiring connections.

 

 

No

No

 

 

Replace control only if all checks

 

are OK.

 

 

 

No

 

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

 

 

 

 

 

 

No

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

 

 

No

Replace control if Code 45 is dis-

played, or if all checks are OK.

 

Clean flame sensor if microamps

 

are below nominal.

No

 

 

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

No

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

No

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

position and repeat process to check

high-stage gas heat operation. (When finished return SW-1 and SW-2 to original desired settings.)

24v should be present across R and Com. If not, check for:

No

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

1.

Open limit switch (LS) – Code 13 or 33.

 

 

 

 

 

2.

Open flame rollout switch (FRS) – Code 13 or 33.

 

 

 

24v should not be present across R and G. If so, set thermostat

 

 

 

FAN to AUTO mode.

 

 

 

A97544

—10—

Page 10
Image 10
Bryant 331JAV, 330JAV Start, Troubleshooting Guide, Electrical Shock Hazard, A97544, Only Qualified And Trained, Code