AIRFLOW
INSTALLATION
POSITION
OF FILTERS
PLENUM
ACCESS DOOR
MOUNTING
SCREWS
RELIEF
BOX
GAS VALVE
CONTROL
W Y R G
WASHABLE
FILTER OR
DISPOSIBLE
MEDIA FILTER
IN FILTER
CABINET
FLUE
COLLAR
BLOCKED
VENT
SAFEGUARD
PRESSURE
SWITCH
FLUE
COLLECTOR
BOX
FILTER
RETAINER
WASHABLE
FILTER
FURNACE
A00293
A88486
Fig. 4—Downflow Filter Arrangement
f. Rinse and let dry. Oiling or coating of filters is not recommended or required.
g.Reinstall filters.
h.Replace blower access door and turn on electrical supply to furnace.
2.
a.Turn off electrical supply to furnace
b.Remove filter cabinet door.
c.Slide filter out of cabinet.
d.If equipped with permanent, washable filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended.
e.If equipped with
f.Slide filter into cabinet.
g.Replace filter cabinet door.
h.Turn on electrical supply to furnace.
3.
a.Turn off electrical supply before removing blower and control access doors.
b.Release filter retainer from clip at front of furnace casing. (See Fig. 5.) For side return, clips may be used on either or both sides of the furnace.
c.Slide filter out.
d.Clean filters by spraying tap water through filter from opposite direction of airflow.
Fig. 5—Model 330JAV Upflow
e. Rinse and let dry. Oiling or coating of filter is not recommended or required.
f.Place filter in furnace.
g.Replace blower and control access doors and turn on electrical supply to furnace.
II. BLOWER MOTOR AND WHEEL
The following items should be performed by a qualified service technician:
For long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are
Clean blower motor and wheel as follows:
1.Turn off electrical supply to furnace.
2.Remove blower access door.
3.Downflow only:
a.Disconnect vent connector from furnace flue collar. (See Fig. 6.)
b.Remove internal vent pipe enclosure cover.
c.Disconnect and remove short piece of vent pipe from within furnace.
d.Disconnect and remove vent pipe enclosure. Push bot- tom side backward to release tabs.
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.
4.Disconnect blower leads from furnace control. Note wire color and location for reassembly. Also, disconnect auxil- iary limit switch leads (downflow only, if present).
All other factory wires can be left connected, but field thermostat connections may need to be disconnected de- pending on their length and routing.
5.Remove 2 screws securing control and transformer support to furnace.
6.Hang control and transformer support to front of furnace casing.