SPECIFICATIONS

SPECIFICATIONS

UNIT SIZE

 

 

 

 

 

036060

 

048080

060100

 

 

 

 

 

 

 

 

 

 

RATINGS AND PERFORMANCE

 

 

 

 

 

 

Gas Input (Btuh)*

 

 

 

High Stage

63,000

 

84,000

105,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Stage

40,500

 

54,000

67,500

 

 

 

 

 

 

 

 

 

 

 

Output Capacity (Btuh)†

 

 

 

High Stage

51,000

 

69,000

86,000

 

 

 

 

 

 

 

 

 

Nonweatherized ICS

 

 

 

Low Stage

33,000

 

44,000

55,000

 

 

 

 

 

 

 

 

 

 

AFUE†

Nonweatherized ICS

80.0

 

80.0

80.0

 

 

 

 

 

 

 

 

 

 

 

Certified Temperature Rise

 

 

 

High Stage

30—60

 

30—60

35—65

Range (°F)

 

 

 

Low Stage

15—45

 

15—45

20—50

 

 

 

 

 

 

 

 

 

 

Certified External Static Pressure

Heat/Cool

0.10/0.50

 

0.15/0.50

0.20/0.50

 

 

 

 

 

 

 

 

 

 

Airflow CFM

 

Heating High/Low

1195/1030

 

1355/1170

1735/1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

1195

 

1580

1950

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

 

 

 

 

Unit Volts— Hertz— Phase

 

 

 

 

 

 

 

115—60—1

 

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range

 

 

 

Min—Max

 

 

104—127

 

 

 

 

 

 

 

 

 

 

 

Maximum Unit Amps

 

 

 

 

 

10.5

 

14.2

17.9

 

 

 

 

 

 

 

 

 

 

Maximum Wire Length (Measured 1 Way)

 

Ft

35

 

26

32

 

 

 

 

 

 

 

 

 

 

 

Minimum Wire Size

 

 

 

 

 

 

14

12

 

 

 

 

 

 

 

 

 

 

Maximum Fuse Size

 

 

 

 

 

 

15

20

 

 

 

 

 

 

 

 

 

 

 

Transformer (24v)

 

 

 

 

 

 

 

40va

 

 

 

 

 

 

 

 

 

 

 

 

External Control

 

 

 

 

Heating

 

 

19va

 

Power Available

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

35va

 

Air Conditioning Blower Relay

 

 

 

 

 

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLS

 

 

 

 

 

 

 

 

 

Limit Control

 

 

 

 

 

 

 

SPST (Auto-Reset)

 

 

 

 

 

 

 

 

 

 

 

 

Heating Blower Control

 

 

 

 

 

 

 

Solid-State Time Operation

 

 

 

 

 

 

 

 

 

 

 

 

Inducer

 

 

 

 

 

 

 

2-Speed

 

 

 

 

 

 

 

 

 

 

 

Burners (Monoport)

 

 

 

 

 

3

 

4

5

 

 

 

 

 

 

 

 

 

 

 

Gas Connection Size

 

 

 

 

 

 

 

1/2-in. NPT

 

 

 

 

 

 

 

 

 

 

 

 

GAS CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-Stage Redundant Gas Valve

 

 

 

 

 

 

 

White-Rodgers

 

 

 

 

 

 

 

 

 

 

 

Min Inlet Pressure (In. wc)

 

 

4.5 (Natural Gas)

 

Max Inlet Pressure (In. wc)

 

 

13.6 (Natural Gas)

 

 

 

 

 

 

 

 

 

 

 

 

Ignition Device

 

 

 

 

 

 

 

Hot Surface

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER DATA

 

 

 

 

 

 

 

 

 

Direct-Drive Motor HP (PSC)

 

 

 

 

 

1/3

 

1/2

3/4

 

 

 

 

 

 

 

 

 

 

 

Motor Full Load Amps

 

 

 

 

 

5.1

 

7.4

11.0

 

 

 

 

 

 

 

 

 

 

 

RPM (Nominal)—Speeds

 

 

 

 

 

 

 

1075—5

 

 

 

 

 

 

 

 

 

 

 

Blower Wheel Diameter x Width (In.)

 

 

10 x 6

 

10 x 8

10 x 6

 

 

 

 

 

 

 

 

 

Filter Size (In.)—Permanent Washable (Supplied)

 

(2) 14 x 20 x 1

(2) 16 x 20 x 1

 

 

 

 

 

 

 

 

 

 

DEALER-INSTALLED ACCESSORIES

 

 

 

 

 

 

Downflow Subbase**

 

 

 

 

 

 

 

KGASB0201ALL

 

 

 

 

 

 

 

 

 

 

 

High-Altitude Pressure Switch Kit‡

 

 

 

 

KGAH5601PSW

 

 

 

 

 

 

 

 

 

 

 

Gas Conversion Kit—Natural-to-Propane

 

 

 

 

KGANP26012SP

 

 

 

 

 

 

 

 

 

 

 

Gas Conversion Kit—Propane-to-Natural

 

 

 

 

KGAPN21012SP

 

*Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 4% for each 1000 ft above sea level. Refer to National Fuel Gas Code Table F4. In Canada, derate the unit 10% for elevations 2000 ft to 4500 ft above sea level.

Capacity in accordance with U.S. Government DOE test procedures.

‡ 5500 ft and higher above sea level.

**Required for installation on combustible floors when no coil box is used, or when any coil box other than a Bryant cased coil is used. ICS—Isolated Combustion System

CONTROLS—THERMOSTATS AND ZONING

 

Auto Changeover, °F/°C, 1-Stage Heat/1-Stage cool — TSTATBBNAC01-B

 

Auto Changeover, °F/°C, 2-Stage Heat/1-Stage Cool — TSTATBBNHP01-B

THERMOSTAT—NON-PROGRAMMABLE

Auto Changeover, °F/°C, 2-Stage Heat/2-Stage cool — TSTATBBN2S01-B

in AC Mode, 3-Stage Heat/2-Stage Cool in HP Mode

 

 

Air Conditioner, 1-Stage Heat/1-Stage Cool, Manual Changeover, °F/°C — TSTATBBBAC01

 

Heat Pump, 2-Stage Heat/1-Stage Cool. Manual Changeover, °F/°C — TSTATBBBHP01*

 

 

 

Auto Changeover, 7-Day Programmable, °F/°C, 1-Stage heat/1-Stage cool — TSTATBBPAC01-B

 

Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat/1-Stage Cool — TSTATBBPHP01-B

 

Auto Changeover, 7-Day Programmable, °F/°C, — TSTATBBP2S01-B

THERMOSTAT-PROGRAMMABLE

2-Stage Heat/2-Stage Cool in AC Mode, 3-Stage Heat/2-Stage Cool in HP Mode

Dual Fuel Thermostat. Includes Outdoor Air Temperature Sensor — TSTATBBPDF01-B*

 

 

Thermidistat™ Control — Non-Programmable/ProgrammableTSTATBBPRH01-B*

 

Thermostat with Humidity Control (For use in Dual Fuel, AC, HP, and 2S applications.

 

Includes Outdoor Air Temperature Sensor.)

 

 

ZONING—2-ZONE

ZONEBB2KIT01, ZONEKIT2ZBDP

 

 

ZONING—4-ZONE

ZONEBB4KIT01

 

 

ZONING—8-ZONE

ZONEBB8KIT01

 

 

—3—