INSTALLATION
This forced air furnace is equipped for use with natural or propane gas at altitudes 0 - 10,000 ft (0 - 3,050m). This furnace is for indoor installation in a manufactured (mobile) or modular home.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible material.
This appliance requires a special venting system. Refer to the installation instructions for parts list and method of installation. This furnace is for use with
Furnace must be installed level, or pitched forward within 1/2 inch of level for proper drainage. Failure will result |
| LEVEL (0") |
|
| ||
in equipment or property damage. |
|
| TO |
|
| |
|
|
|
| 1/2" MAX |
|
|
|
|
|
|
|
| FRONT |
|
|
|
| DOWNFLOW |
|
|
| MINIMUM INCHES CLEARANCE TO | This furnace is approved for |
|
| ||
| DOWNFLOW installation. 1" |
|
| |||
| COMBUSTIBLE CONSTRUCTION |
|
| |||
|
|
| TOP/PLENUM |
|
| |
DOWNFLOW POSITION: |
|
|
|
| ||
|
|
|
|
| ||
* | Mimimum front clearance for service 30 inches (762mm). |
| 0" |
|
|
|
|
| B A C K |
|
| ||
† For installation on combustible floors only when installed on special base No. KGASB0201ALL, |
|
|
|
| ||
| Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC. |
|
|
|
| CE |
|
|
|
|
|
| A |
|
|
|
|
|
| N |
|
|
|
|
| R | |
|
|
|
| U | T | |
|
|
|
| F |
| |
| MANUFACTURED MOBILE HOME STANDARDS |
|
|
|
| N |
|
|
|
|
| O | |
|
|
|
|
| R | |
|
|
|
|
|
| F |
| E |
I | D |
S |
|
0"
This furnace must be installed in accordance with the manufacturer's instructions and Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 or, when such standard is not applicable, the ANSI A225.1, Standard for Manufactured Home Installation (Manufactured Home Sites, Communities and
This furnace must be installed with a direct vent (combustion air and flue) system, and use a factory accessory termination kit.
SIDE
0"
Clearance in inches
|
|
| S E | R VI |
|
|
|
|
| C E * | |
F R | O N |
|
|
| |
| T |
|
| 30 | |
|
|
|
| MIN |
3"
BOTTOM
0"
†
Condensate Trap
on LEFT Side
COLLECTOR BOX
DRAIN TUBE
CONDENSATE TRAP
INDUCER HOUSING DRAIN TUBE
BURNER ENCLOSURE PRESSURE REFERENCE
TUBE ASSEMBLY
|
|
|
| TUBE ROUTING |
|
|
|
|
|
| Condensate Trap | ||
|
|
|
|
|
|
|
|
|
|
|
|
| on RIGHT Side |
|
|
|
|
| BURNER ENCLOSURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| PRESSURE |
|
|
|
|
|
|
| |
|
|
|
|
| REFERENCE TUBE |
|
|
|
|
|
|
| |
|
|
|
|
| ASSEMBLY |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| CAP / PLUG |
|
|
|
|
| CAP / PLUG |
|
|
|
|
| LOWER COLLECTOR BOX | ||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| LOWER COLLECTOR |
|
|
|
|
|
| PRESSURE TUBE | ||
|
|
| BOX PRESSURE TUBE |
|
|
|
|
|
|
| |||
|
|
|
| UPPER COLLECTOR |
|
|
|
|
| UPPER COLLECTOR BOX | |||
|
|
|
|
|
|
|
|
| |||||
|
|
| BOX PRESSURE TUBE |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| PRESSURE TUBE | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| GAS VALVE |
|
|
| GAS VALVE | |||||
|
|
|
|
|
|
| |||||||
|
|
|
|
| COLLECTOR BOX |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| DRAIN TUBE |
|
|
|
|
| COLLECTOR BOX EXTENSION DRAIN | ||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| INDUCER HOUSING |
|
|
|
|
|
| TUBE | |
|
|
|
|
|
|
|
|
|
|
| DRAIN TUBES ROUTED IN | ||
|
|
|
|
| DRAIN TUBE |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| FRONT OF GAS VALVE | ||
|
|
|
|
| DRAIN TUBE |
|
|
|
|
|
| CONDENSATE TRAP | |
|
|
|
|
| COUPLING |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
NOTE: 1. All tubing must be connected securely and routed to avoid kinks and traps. | |
| A99001e |
| ||
|
| |
| For Use with | |
For Use with | ||
| For Use with | |
| For Use with | |
For Use with | ||
For Use with | ||
| ||
| For Use with | |
|
| |
with Humidity Control |
|