COMBUSTION-AIR AND VENT PIPING

MAXIMUM ALLOWABLE PIPE LENGTH (FT)

ALTITUDE

 

 

 

 

 

NUMBER OF 90° ELBOWS

 

 

ABOVE SEA

 

 

PIPE DIA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL (FT)

UNIT SIZE

TERMINATION TYPE

(IN.)*

1

2

 

3

4

 

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

1-1/2

10

NA

 

NA

NA

 

NA

NA

0 to 2000

048080

2 Pipe or 2-In. Concentric

2

55

50

 

35

30

 

30

20

 

060080

 

2-1/2

70

70

 

70

70

 

70

70

 

 

 

 

 

 

036080

 

2

49

44

 

30

25

 

25

15

2001 to 3000

048080

2 Pipe or 2-In. Concentric

 

 

 

 

 

 

 

 

 

2-1/2

70

70

 

70

70

 

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

46

41

 

28

23

 

22

13

3001 to 4000

048080

2 Pipe or 2-In. Concentric

2-/12

70

70

 

70

70

 

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

44

39

 

26

21

 

20

11

4001 to 5000†

048080

2 Pipe or 2-in Concentric

 

 

 

 

 

 

 

 

 

2-1/2

70

70

 

70

70

 

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

41

36

 

23

18

 

17

8

5001 to 6000†

048080

2 Pipe or 2-In. Concentric

 

 

 

 

 

 

 

 

 

2-1/2

70

70

 

70

70

 

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

38

33

 

21

16

 

15

6

6001 to 7000†

048080

2 Pipe or 2-In. Concentric

2-1/2

70

70

 

68

67

 

66

64

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

36

31

 

19

14

 

12

NA

7001 to 8000†

048080

2 Pipe or 2-In. Concentric

 

 

 

 

 

 

 

 

 

2-1/2

66

65

 

63

62

 

60

59

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

 

2

33

28

 

17

12

 

10

NA

8001 to 9000†

048080

2 Pipe or 2-In. Concentric

 

 

 

 

 

 

 

 

 

2-1/2

62

60

 

58

56

 

55

53

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9001 to

036080

 

2

30

25

 

14

9

 

7

NA

10,000†

048080

2 Pipe or 2-In. Concentric

2-1/2

57

55

 

53

51

 

49

47

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Disk usage—Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag).

Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA—Not Allowed; pressure switch will not make.

NOTES:

1.Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2.Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.

3.Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

4.Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

5.The minimum pipe length is 5 ft for all applications.

MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION

IN WINTER DESIGN TEMPERATURE AMBIENT*

 

WINTER DESIGN

MAX PIPE

 

 

 

TEMPERATURE

DIAMETER

WITHOUT

WITH 3/8-IN. OR

UNIT SIZE

(°F)

(IN.)

INSULATION

THICKER INSULATION†

036080

20

2-1/2

70

70

 

 

 

 

048080

0

2-1/2

47

70

060080

 

 

 

 

–20

2-1/2

28

70

 

 

 

 

 

 

*Pipe length (ft) specified for maximum vent pipe lengths located in unconditioned spaces. Vent pipes located in unconditioned space cannot exceed the

total allowable pipe length as specified in Maximum Allowable Pipe Length table.

† Insulation thickness based on R value of 3.5 per in.