359AAV
8.Turn on gas and electrical supplies to furnace.
9.Verify igniter operation by initiating furnace control
10.Replace main furnace door.
Procedure 7 — Electrical Controls and Wiring
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than 1 electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for
NOTE: If polarity is not correct, STATUS LED on furnace control board will flash rapidly and prevent furnace from operating. The control system also requires an earth ground for proper operation of furnace control and flame sensor.
The
With power to unit disconnected, check all electrical connections for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble connection, clean all parts, strip wire, and reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through 1 complete operating cycle for proper operation.
Procedure 8 — Checking Heat Tape Operation (If Applicable)
In applications where the ambient temperature around the furnace is 32°F (0°C) or lower, freeze protection measures are required. If heat tape has been applied, check to ensure it will operate when low temperatures are present.
!CAUTION
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage or property damage.
If this furnace is to be operated in an unconditioned space where the ambient temperatures may be 32°F (0°C) or lower, freeze protection measures must be taken. (See Fig. 19.) See CONDENSATE DRAIN PROTECTION section of Installation,
NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1.Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
2.Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3.Check that heat tape power supply circuit is on.
Procedure 9 — Winterizing
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage.
Freezing condensate left in the furnace will damage the furnace.
If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F (0°C) or below, winterize as follows:
1.Turn off electrical supply to furnace.
2.Remove main furnace door.
3.Disconnect the 1/2” I.D. rubber hose from the vent drain fitting (or tee) that is located downstream of the combustion blower. Insert a funnel into the hose and pour four (4) ounces of sanitary type (RV) antifreeze into the condensate trap. Reconnect the 1/2” I.D. rubber hose to the stub the vent drain fitting. Secure with the hose clamp.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type). Failure of plastic components may occur.
4.Disconnect the 5/8” I.D. rubber hose from the condensate trap. Insert a funnel into the hose and pour four (4) ounces of sanitary type (RV) antifreeze into the plastic transition box. Squeeze the hose together near the and quickly reconnect the 5/8” I.D. rubber hose to the stub on the condensate trap. Secure with the hose clamp.
5.When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.
WIRING DIAGRAM
See Fig. 20 for Wiring Diagram.
TROUBLESHOOTING
Use the Troubleshooting Guide, the status code LED on the control and the Component Test to isolate furnace operation problems.
A. Status Codes
For an explanation of status codes, refer to service label located on front of blower door or Fig. 21.
NOTE: Removing the blower access door will open the blower access door switch and terminate
NOTE: NO thermostat signals should be present at control and all blower off delays must be completed to view previous codes.
18