Bryant 359AAV Procedure 3 - Cleaning Burners, Bottom Filter Arrangement, Speed Selector

Models: 359AAV

1 22
Download 22 pages 31 Kb
Page 4
Image 4
Fig. 2 - Bottom Filter Arrangement

359AAV

Center Clip side-to-side

9”Fig. 3 - Filter Installed for Side Inlet

(228.6 mm)

A07691

 

Fig. 2 - Bottom Filter Arrangement

Filter Rack

End Cap

A07690

Fig. 3 - Filter Installed for Side Inlet

f. Remove blower wheel from housing.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in furnace component failure.

The blower wheel should not be dropped or bent as balance will be affected.

g.Clean wheel per instructions on degreaser cleaner. Do not get degreaser cleaner in motor.

9.Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Be sure to reattach ground wire. Tighten setscrew to 140 to 160 in.-lb torque.

10.Reinstall blower assembly in furnace.

11.Reinstall control box, transformer, and door switch assembly on blower shelf.

12.Reinstall condensate trap and tubing if previously removed.

a.Reinstall condensate trap in hole in blower shelf.

b.Connect condensate trap drain tubes. See Fig. 6, 7, or 8.

NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.

c.Connect field drain to condensate trap.

13.Reconnect wires.

Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected. (See Fig.20.)

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit component damage.

Heating speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate.

Table 1 – Speed Selector

COLOR

SPEED

FACTORY

ATTACHED TO

Black

High

Cool

Orange

Medium High

Heat

Blue

Medium Low

M1

Red

Low

M2

White

Common

Com

14.Turn on electrical supply. Manually close blower access door switch. Use a piece of tape to hold switch closed. Check for proper rotation by jumpering R to G.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes.

15.If furnace is operating properly, remove tape to release blower access door switch, remove jumper across R to G, and replace blower access door.

Procedure 3 — Cleaning Burners

The following items should be performed by a qualified service technician. If burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:

1.Turn off gas and electrical supplies to furnace.

2.Remove main furnace door.

3.Using backup wrench, disconnect gas supply pipe from furnace gas control valve.

!CAUTION

ELECTRICAL SHOCK, UNIT DAMAGE HAZARD

Failure to follow this caution may result in personal injury or furnace component damage.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.