4.If furnace is operating properly and LED indicates proper operation, replace control access door.
5.Component Test can also be initiated by performing the following:
a.Remove control access door.
b.Remove blower access door.
c.Manually close blower access door switch.
WARNING: Blower access door switch opens
d.BRIEFLY short (jumper) TEST, 3/16 in. quick connect terminal on control (adjacent to LED status light), and
NOTE: If TEST to
e. Component Test will function as described in item 2 above.
f.Check LED status.
g.If LED status indicates proper operation, RELEASE BLOWER ACCESS DOOR SWITCH, replace blower access door, and replace control access door.
WIRING DIAGRAMS
Refer to Fig. 5, 6, and 7 for wiring diagrams.
TROUBLESHOOTING
Refer to service label. (See Fig. 8.) The Troubleshooting Guide can be a useful tool in isolating furnace operation problems. Beginning with the word ªStart,º answer each question and follow the appropriate arrow to the next item.
The Guide will help you identify the problem or failed component. After replacing any component, verify correct operation sequence.
Ð9Ð