21
C99024
ELECTRICAL DATA574B (STANDARD) ELECTRICAL DATA
UNIT
SIZE
574B
V-PH-Hz
VOLTAG E
RANGE COMPRESSOR OUTDOOR FAN
MOTOR
INDOOR FAN
MOTOR POWER SUPPLY
Min Max RLA LRA FLA FLA MCA
MAX FUSE
OR BKR
024 208/230160 187 253 13.5 61.0 0.8 4.3 22.0/22.0 30/30
030 208/230160 187 253 16.9 73.0 0.8 4.3 25.0/25.0 30/30
036 208/230160 187 253 15.9 83.0 0.8 6.8 28.7/28.7 35/35
208/230360 187 253 12.2 77.0 0.8 6.8 22.9/22.9 30/30
042 208/230160 187 253 22.4 105.0 0.8 6.8 35.6/35.6 45/45
208/230360 187 253 15.4 88.0 0.8 6.8 26.9/26.9 35/35
048 208/230160 187 253 21.3 109.0 1.6 6.8 35.0/35.0 45/45
208/230360 187 253 14.7 91.0 1.6 6.8 26.8/26.8 35/35
060 208/230160 187 253 27.0 145.0 1.6 9.1 44.5/44.5 60/60
208/230360 187 253 18.1 123.0 1.6 9.1 33.3/33.3 40/40
452=5v
457=7v
455=2v
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-

age is greater than 2%.

Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage = 3
1371
=3
= 457
Determine maximum deviation from average voltage.
(AB) 457
(BC) 464
(AC) 457
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x 457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
®
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.
If power distribution voltage to unit varies from rated heater voltage,
heater KW will vary accordingly.