Step 6 — Provide for Condensate Disposal
NOTE: Ensure that
The
mm)lower than the
If the installation requires draining the condensate water away from the unit, install a
High-Voltage Connections
The unit must have a separate electrical service with a
The
See unit wiring label (Fig.
Single phase units:
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. (25 mm) every 10 ft (3 m) of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season
Step 7 — Install Electrical Connections
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
TWO POWER | EQUIP GR |
LEADS |
CONTROL BOX
POWER
SUPPLY
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. | Make all electrical connections in accordance with NEC |
| NFPA 70 (latest edition) and local electrical codes |
| governing such wiring. In Canada, all electrical |
| connections must be in accordance with CSA standard |
| C22.1 Canadian Electrical Code Part 1 and applicable |
| local codes. Refer to unit wiring diagram. |
2. | Use only copper conductor for connections between |
|
WIRING LABEL
SPLICE BOX
WHT(W1) | W1 |
| |
VIO (W2) | W2 |
| |
YEL(Y) | Y |
| |
GRN(G) | G |
| |
RED(R) | R |
| |
BRN(C) | C |
| |
ORN(O) | O |
| |
BLU(DH) | DH |
| |
GRA(Y2) | |
| |
| Only |
THERMOSTAT (TYPICAL)
| NOT USE ALUMINUM WIRE. |
3. | Be sure that |
| operating voltage range indicated on unit rating plate. On |
| |
| percent. Consult local power company for correction of |
| improper voltage and/or phase imbalance. |
4. | Do not damage internal components when drilling |
| through any panel to mount electrical hardware, conduit, |
| etc. |
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC,NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
A09071
Fig. 9 - High- and Control-Voltage Connections
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.
6.Connect field wire L2 to blue wire from compressor.
9