Bryant 650A warranty HEAT PUMP HEATING PERFORMANCE Continued

Models: 650A

1 20
Download 20 pages 45.05 Kb
Page 17
Image 17
—17—

HEAT PUMP HEATING PERFORMANCE Continued

INDOOR

 

 

 

 

 

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

AIR

 

–3

 

 

 

7

 

 

17

 

 

 

27

 

 

37

 

 

 

 

47

 

 

 

 

57

 

 

 

67

 

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

 

 

MBtuh†

Pwr

MBtuh†

Pwr

MBtuh†

 

Pwr

MBtuh†

Pwr

MBtuh†

Pwr

MBtuh†

 

Pwr

MBtuh†

Pwr

MBtuh†

Pwr

EDB

 

CFM

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

 

Kw† Total

 

Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

Total

Int*

Kw†

 

 

 

 

 

 

 

650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section

 

 

 

 

 

 

65

 

1400

18.5

17.0

2.86

22.9

21.1

2.99

27.9

25.4

 

3.11

33.5

 

29.8

3.26

40.2

36.6

3.45

48.2

 

48.2

3.69

53.8

 

53.8

4.34

53.1

53.1

4.20

 

1600

18.7

17.2

2.87

23.2

21.3

2.98

28.1

25.6

 

3.10

33.8

 

30.1

3.23

40.7

37.0

3.41

48.7

 

48.7

3.64

54.4

 

54.4

4.28

53.7

53.7

4.14

 

 

1800

18.9

17.4

2.89

23.4

21.5

2.99

28.4

25.9

 

3.10

34.1

 

30.3

3.23

41.0

37.3

3.40

49.1

 

49.1

3.63

54.9

 

54.9

4.26

54.1

54.1

4.12

70

 

1400

18.1

16.7

3.03

22.7

20.9

3.16

27.6

25.2

 

3.29

33.2

 

29.4

3.44

39.8

36.2

3.64

47.5

 

47.5

3.89

54.3

 

54.3

4.57

52.3

52.3

4.40

 

1600

18.4

16.9

3.03

23.0

21.1

3.15

27.8

25.4

 

3.27

33.5

 

29.7

3.41

40.2

36.5

3.60

48.0

 

48.0

3.83

53.6

 

53.6

4.50

52.9

52.9

4.33

 

 

1800

18.6

17.1

3.05

23.2

21.3

3.16

28.1

25.6

 

3.27

33.8

 

30.0

3.41

40.5

36.9

3.58

48.4

 

48.4

3.81

54.1

 

54.1

4.47

53.3

53.3

4.31

75

 

1400

17.7

16.3

3.19

22.4

20.6

3.33

27.4

24.9

 

3.48

32.8

 

29.2

3.64

39.3

35.7

3.84

46.8

 

46.8

4.09

52.2

 

52.2

4.80

51.4

51.4

4.62

 

1600

18.0

16.6

3.20

22.7

20.9

3.33

27.6

25.2

 

3.46

33.1

 

29.4

3.60

39.7

36.1

3.79

47.4

 

47.4

4.04

52.8

 

52.8

4.72

52.0

52.0

4.54

 

 

1800

18.2

16.8

3.22

22.9

21.1

3.33

27.8

25.4

 

3.45

33.4

 

29.7

3.59

40.0

36.4

3.77

47.8

 

47.8

4.01

53.3

 

53.3

4.69

52.5

52.5

4.51

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

Section

 

 

 

Size

 

 

Capacity

 

 

 

Power

 

 

 

 

Section

 

 

Size

 

 

Capacity

 

 

Power

 

 

FV4ANF

 

 

005

 

 

 

1.00

 

 

 

1.00

 

 

 

 

FX4ANB

 

 

060

 

 

1.01

 

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F(A,B)4AN(F,B,C)

 

 

060

 

 

 

1.02

 

 

 

1.10

 

 

 

 

FX4ANF

 

 

048

 

 

1.01

 

 

1.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FB4ANB

 

 

070

 

 

 

1.01

 

 

 

1.02

 

 

 

 

CE3AA

 

 

060

 

 

1.01

 

 

1.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BN(F,B)

 

 

060

 

 

 

1.01

 

 

 

1.09

 

 

 

CJ5A/CK5A/CK5BA

 

060

 

 

1.01

 

 

1.03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BNB

 

 

070

 

 

 

1.01

 

 

 

1.02

 

 

 

CJ5A/CK5A/CK5BN

 

060

 

 

1.02

 

 

1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4CNB

 

 

006

 

 

 

1.01

 

 

 

0.96

 

 

 

CJ5A/CK5A/CK5BX

 

060

 

 

1.02

 

 

1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4CNF

 

 

005

 

 

 

1.01

 

 

 

1.01

 

 

 

 

CK3BA

 

 

060

 

 

1.01

 

 

1.03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FV4ANB

 

 

006

 

 

 

1.01

 

 

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section

 

 

 

 

 

 

65

 

1750

24.4

22.4

3.73

30.9

28.4

3.88

37.9

34.6

 

4.05

45.0

 

40.0

4.24

52.6

47.9

4.45

60.8

 

60.8

4.68

58.2

 

58.2

4.52

56.3

56.3

4.47

 

2000

24.9

22.9

3.76

31.5

28.9

3.90

38.5

35.1

 

4.05

45.7

 

40.6

4.22

53.2

48.4

4.41

61.6

 

61.6

4.61

59.0

 

59.0

4.44

57.1

57.1

4.37

 

 

2250

25.3

23.3

3.80

31.9

29.3

3.93

39.0

35.5

 

4.06

46.2

 

41.0

4.23

53.7

48.9

4.39

62.2

 

62.2

4.58

59.6

 

59.6

4.39

57.8

57.8

4.31

70

 

1750

23.4

21.5

3.92

30.0

27.6

4.09

37.0

33.7

 

4.27

44.2

 

39.2

4.46

52.0

47.3

4.70

60.0

 

60.0

4.94

57.4

 

57.4

4.76

55.4

55.4

4.71

 

2000

23.8

21.9

3.95

30.5

28.0

4.10

37.6

34.3

 

4.26

44.8

 

39.8

4.44

52.5

47.8

4.65

60.7

 

60.7

4.87

58.1

 

58.1

4.67

56.2

56.2

4.60

 

 

2250

24.3

22.3

4.00

31.0

28.5

4.13

38.1

34.7

 

4.28

45.4

 

40.3

4.45

53.1

48.3

4.63

61.4

 

61.4

4.83

58.8

 

58.8

4.62

56.9

56.9

4.53

75

 

1750

22.2

20.5

4.12

28.9

26.6

4.30

36.0

32.9

 

4.49

43.2

 

38.4

4.70

51.3

46.7

4.96

59.2

 

59.2

5.21

56.5

 

56.5

5.02

54.5

54.5

4.95

 

2000

22.7

20.9

4.15

29.5

27.1

4.31

36.7

33.4

 

4.49

43.9

 

39.0

4.67

51.9

47.2

4.90

59.9

 

59.9

5.13

57.3

 

57.3

4.92

55.3

55.3

4.83

 

 

2250

23.2

21.3

4.20

30.0

27.5

4.34

37.2

33.9

 

4.50

44.5

 

39.5

4.67

52.4

47.7

4.88

60.6

 

60.6

5.09

57.9

 

57.9

4.86

56.0

56.0

4.76

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

Section

 

 

 

Size

 

 

Capacity

 

 

 

Power

 

 

 

 

Section

 

 

Size

 

 

Capacity

 

 

Power

 

 

FV4ANB

 

 

006

 

 

 

1.00

 

 

 

1.00

 

 

 

 

FX4ANB

 

 

060

 

 

1.00

 

 

1.03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FB4ANB

 

 

070

 

 

 

1.00

 

 

 

1.03

 

 

 

CC5A/CD5AW

 

 

060

 

 

0.98

 

 

1.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BNB

 

 

070

 

 

 

1.00

 

 

 

1.03

 

 

 

CJ5A/CK5A/CK5BX

 

060

 

 

0.98

 

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4CNB

 

 

006

 

 

 

0.99

 

 

 

0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.

The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to obtain total system kilowatts.

EDB—Entering Dry Bulb

NOTE: The performance shown includes the PressureGuard™ cycling the outdoor fan. The ambient temperature that the outdoor fan cycles depends on the outdoor/indoor combination, indoor airflow, installation practices, and system mainte- nance, all of which affect system performance.