T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
5 60-24858
Models:
See Table 4.
Electrical Ratings:
Switch Contacts: 2.5A at 30 Vac
(
7.5A inrush
)
.
LED Li
g
hts
(
Optional
)
: 30 Vac.
Switches: Two slide switches
(
one switch on Q674G and K;
no switches on Q674D
)
operated b
y
levers. Switch position
is shown on scaleplate.
Mounting: Desi
g
ned to mount horizontall
y
on an outlet box
or the wall. Adapter plate assembl
y
available for mountin
g
on a vertical outlet box
(
see Subbase Accessor
y)
.
Finish: Dark brown or
g
ra
y
.
Dimensions in in. (mm): 3-1/2
(
89
)
hei
g
ht; 5-5/8
(
143
)
width;
5/16
(
8
)
depth. See Fi
g
. 1.
Table 4. Q674 Subbase Specifications.
Fast c
y
clin
g
. Electric Heat 0.12-
0.6A 0.12-
0.6A
T874GHeat pump, cool
chan
g
eover, with fast c
y
clin
g
.T872G Heat Pump or
Standard 21
1b0-1.0Ac0.1-1.2A 0-1.0A
Fixed anticipator for H2. 0.1-1.5A
Fast c
y
clin
g
.0.12-
0.6A
T874HUse with Q674C. T872H Heat Pump or
Standard 11
1b0-1.0Ac0-1.0A
T874JHeat pump. None Heat Pump 2 1 2d0-1.0Ae0-1.5Ac0-1.0Ac
T874KHeat pump. None Heat Pump 2 1 1b0.1-1.2A 0-1.5Ac0-1.5A
T874LHeat pump. None Heat Pump 2 1 0.1-1.2A 0.1-1.2A 0-1.5A
T874NHeat pump, heat
chan
g
eover. T872N Heat Pump 2 1 1b0.1-1.2A 0.1-1.2A 0-1.0A
T874PHeat pump. None Heat Pump 2 1 0.1-1.2A 0.1-1.2A 0-1.5A
T874QNi
g
ht setback heatin
g
. T872Q Standard 1e——0.1-1.2A ———
T874RHeat pump. T872R Heat Pumpf210-1.5Ac0.1-1.2A 0-1.5A
T874STwo-speed compressor heat
pump. None Heat Pump 2 2 1
0-1.2Ac0-1.2Ac0-1.2A 0-1.0A
T874VStandard. None Standard 1—— —0-1.5A
T874WHeat pump and standard.
Ni
g
ht setback heatin
g
.T872W Heat Pump or
Standard 320-1.2Ab0-1.2Ac,d 0-1.2A 0-1.0A
aDepartment of Defense.
bChan
g
eover sta
g
e operates with heatin
g
.
cFixed volta
g
e t
y
pe anticipation.
dChan
g
eover sta
g
e operates with heatin
g
; a secondar
y
chan
g
eover is provided in coolin
g
switch.
eProvides ni
g
ht setback used with standard T874 and timer-operated remote switchin
g
.
fManual chan
g
eover sta
g
euse Q674B,L subbase.
gChan
g
eover sta
g
e operates with coolin
g
.Q674 Subbases
Models and Options Replaces Application
Switch Positions
Use WithSystem Fan
Q674AStandard and TRADELINE®.
Indicator LEDs. Q672A Standard HEAT-AUTO-COOL AUTO-ON T874A-D
Q674BStandard and TRADELINE. Q672B Standard HEAT-OFF-COOL AUTO-ON T874A-D
Provision for fan rela
y
operation from Heat Pump T874G,H,L,R
external fan switch
(
isolate G terminal
)
. OVERRIDE-HEAT- AUTO-ON T874P
Indicator LEDs. OFF-COOL
Q674CStandard and TRADELINE. Q672C Standard OFF-AUTO AUTO-ON T874A-H,W
Indicator LEDs. Heat Pump OVERRIDE-AUTO- AUTO-ON T874K,L,N
OFF T874P
Q674DStandard and TRADELINE.
For use when subbase switchin
g
is not
re
q
uired.
Q672D Standard No ne None T874A-F