B.STEAM PERFORMANCE DATA

Table 3: Steam Performance Data -- High Motor Speed

Performance Data at Standard Conditions of 2 lb. Steam and 60°F Entering Air

 

 

 

 

 

 

 

 

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max.

 

Heat

 

Outlet

Final Air

 

Model

Model

 

Sq. Ft.

Sound

Mounting

Spread at

 

Velocity

Temp.

Condensate

Type

Number

BTU/Hr.

EDR

Class**

Height (ft)*

Max. Height*

Cfm

(Fpm)

(°F)

lb/hr

 

BH-18

18,000

75

II

 

9

 

17

400

510

102

18

 

BH-24

24,000

100

II

 

9

 

18

450

580

109

25

 

BH-33

33,000

138

II

 

10

 

20

630

510

109

35

DELIVERY

BH-47

47,000

196

III

 

12

 

25

730

600

120

49

BH-63

63,000

263

III

 

14

 

29

1120

605

112

66

 

 

 

 

BH-86

86,000

358

III

 

15

 

31

1340

730

119

89

AIR

BH-108

108,000

450

III

 

15

 

32

1550

625

125

111

BH-121

121,000

504

III

 

16

 

33

1775

715

123

126

HORIZONTAL

 

 

BH-165

165,000

688

IV

 

17

 

34

2500

750

121

170

 

 

 

 

BH-193

193,000

804

IV

 

18

 

37

2900

870

122

200

 

BH-258

258,000

1075

V

 

19

 

40

3900

920

121

267

 

BH-290

290,000

1208

V

 

20

 

44

4300

1010

122

300

 

BH-340

340,000

1417

V

 

20

 

46

5130

965

121

352

 

BV-42

42,000

175

II

11

 

15

17

 

11

950

779

103

43

 

BV-59

59,000

246

II

13

 

18

20

 

13

1150

943

111

61

DELIVERY

BV-78

78,000

325

II

14

 

19

22

 

14

1550

992

110

81

 

 

 

 

BV-95

95,000

396

II

16

 

21

24

 

16

1775

1136

113

99

 

BV-139

139,000

579

III

18

 

24

27

 

18

2500

1284

116

144

AIR

BV-161

161,000

671

III

21

 

28

31

 

21

2900

1490

115

167

BV-193

193,000

804

IV

23

 

31

34

 

23

3900

1643

109

200

VERTICAL

 

 

BV-279

279,000

1163

V

30

 

37

45

 

30

5800

2040

107

288

 

BV-212

212,000

883

IV

25

 

33

37

 

25

4300

1812

109

219

 

BV-247

247,000

1029

IV

26

 

34

39

 

26

5130

1805

107

256

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-333

333,000

1388

V

30

 

37

45

 

30

6600

1968

110

345

 

BV-385

385,000

1604

VI

30

 

36

45

 

30

7860

1930

106

398

 

BV-500

500,000

2083

VI

37

 

44

56

 

37

10790

2490

103

518

 

BV-610

610,000

2542

VI

36

 

43

54

 

36

12350

2345

106

631

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4: Steam Performance Data -- Reduced Motor Speed

Performance Data at Standard Conditions of 2 lb. Steam and 60°F Entering Air

 

 

 

 

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max.

Heat

 

Outlet

Final Air

 

Model

Model

 

Sq. Ft.

Sound

Mounting

Spread at

 

Velocity

Temp.

Condensate

Type

Number

BTU/Hr.

EDR

Class**

Height (ft)*

Max. Height*

Cfm

(Fpm)

(°F)

lb/hr

 

BH-18

14,800

62

I

9

12

310

395

104

15

DELIVERY

BH-24

19,700

82

I

9

13

350

455

112

21

BH-33

27,100

113

I

10

14

490

395

111

29

 

 

BH-47

38,500

161

II

12

18

565

465

123

40

AIR

BH-63

51,700

216

II

14

21

870

470

115

54

BH-86

70,500

294

II

15

22

1040

570

123

73

HORIZONTAL

BH-193

158,300

659

III

18

26

2310

695

123

164

 

BH-108

88,600

369

II

15

23

1240

500

126

91

 

BH-121

99,200

413

II

16

23

1415

570

125

103

 

BH-165

135,300

564

III

17

24

1990

600

123

139

 

 

 

 

 

 

 

 

 

 

 

*Units with horizontal louvers open 30° from vertical plane, vertical types equipped with cone jet deflector, blades fully opened are shown in bold.

Non-bolded mounting height/spread data is for units without deflectors. Please see page 21 for additional outlet accessory

performance data.

** See page 7 for Sound Class Definitions.

11

 

Page 11
Image 11
Burnham BV, BH manual Steam Performance Data -- High Motor Speed, Steam Performance Data -- Reduced Motor Speed