F.HOT WATER PERFORMANCE DATA (at Standard Conditiions of 200°F Entering Water, 60°F Entering Air and 20°F Water Temperature Drop)

Table 9: Hot Water Performance Data -- High Motor Speed

 

 

 

 

WATER DATA

 

 

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drop

 

 

Max.

Heat

 

 

Outlet

Final Air

Model

Model

 

 

(ft. of

Min/Max

Sound

Mounting

Spread at

 

Velocity

Temp.

Type

Number

BTU/Hr.

GPM

water)

GPM

Class**

Height (ft.)*

Max. Height*

Cfm

(Fpm)

(°F)

 

BH-18

13,000

1.3

0.49

0.3/5.0

II

 

9

18

 

400

500

90

DELIVERY

BH-24

17,300

1.7

0.83

0.3/5.0

II

 

10

20

 

450

570

96

BH-33

24,500

2.5

0.12

0.4/10.0

II

 

11

22

 

630

495

96

 

 

 

 

BH-47

33,800

3.4

0.21

0.4/10.0

III

 

13

26

 

730

580

103

 

BH-63

46,500

4.7

0.47

0.5/15.0

III

 

15

30

 

1120

590

98

AIR

BH-86

61,900

6.2

0.79

0.5/15.0

III

 

16

31

 

1340

710

103

BH-108

81,000

8.1

0.85

0.5/20.0

III

 

16

33

 

1550

605

108

 

 

 

HORIZONTAL

BH-121

90,000

9.0

1.04

0.7/20.0

III

 

17

36

 

1775

690

107

BH-165

133,000

13.3

2.48

2.0/30.0

IV

 

18

38

 

2500

735

109

 

 

 

 

BH-193

156,000

15.6

3.35

2.0/30.0

IV

 

19

40

 

2900

850

110

 

BH-258

198,000

19.8

3.54

2.5/40.0

V

 

20

42

 

3900

895

107

 

BH-290

224,000

22.4

4.45

2.5/40.0

V

 

21

46

 

4300

990

108

 

BH-340

273,000

27.3

3.24

2.5/50.0

V

 

22

50

 

5130

945

109

 

BV-42

30,500

3.1

0.09

0.5/10.0

II

11

 

15

17

 

11

950

776

91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-59

44,300

4.5

0.18

0.8/15.0

II

14

 

19

21

 

15

1150

940

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-78

58,500

6.0

0.43

1.0/20.0

II

15

 

21

23

 

16

1550

990

96

DELIVERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-95

71,000

7.2

0.61

1.3/25.0

II

17

 

23

25

 

17

1775

1132

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-139

111,000

11.3

0.84

1.0/30.0

III

18

 

25

28

 

19

2500

1281

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-161

128,800

13.1

1.11

1.3/40.0

III

22

 

30

33

 

21

2900

1488

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

BV-193

142,700

14.5

0.81

1.5/50.0

IV

24

 

33

36

 

24

3900

1640

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-212

159,000

16.1

0.98

2.0/60.0

IV

25

 

35

37

 

25

4300

1809

96

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-247

197,000

19.9

1.65

2.0/60.0

IV

27

 

36

40

 

27

5130

1803

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-279

220,000

22.2

2.01

2.3/75.0

V

31

 

39

47

 

31

5800

2037

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-333

265,000

26.7

1.27

2.8/75.0

V

30

 

38

46

 

30

6600

1966

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-385

308,000

31.1

1.68

3.3/75.0

VI

33

 

40

49

 

33

7860

1928

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-500

403,000

40.9

2.32

3.0/100.0

VI

40

 

48

60

 

40

10790

2487

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-610

459,000

46.3

2.42

6.0/100.0

VI

39

 

47

58

 

40

12350

2343

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 10: Hot Water Performance Data -- Reduced Motor Speed

 

 

 

WATER DATA

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

Drop

 

Max.

Heat

 

Outlet

Final Air

Model

Model

 

 

(ft. of

Sound

Mounting

Spread at

 

Velocity

Temp.

Type

Number

BTU/Hr.

GPM

water)

Class**

Height (ft.)*

Max. Height*

Cfm

(Fpm)

(°F)

DELIVERY

BH-18

10,660

1.3

0.49

I

9

13

310

390

92

BH-24

14,186

1.7

1.83

I

10

14

350

450

98

 

 

BH-33

20,090

2.5

0.12

I

11

16

490

390

98

AIR

BH-47

27,716

3.4

0.21

II

13

18

565

455

105

BH-63

38,130

4.7

0.47

II

15

21

870

460

101

HORIZONTAL

BH-86

50,758

6.2

0.79

II

16

22

1040

550

105

 

 

BH-108

66,420

8.1

0.85

II

16

23

1240

485

110

 

BH-121

73,800

9.0

1.04

II

17

26

1415

555

108

 

BH-165

109,060

13.3

2.48

III

18

27

1990

590

111

 

BH-193

127,920

15.6

3.35

III

19

28

2310

680

111

*Units with horizontal louvers open 30° from vertical plane, vertical types equipped with cone jet deflector, blades fully opened are shown in bold.

Non-bolded mounting height/spread data is for units without deflectors. Please see page 21 for additional outlet accessory performance data.

**See page 7 for Sound Class Definitions.

17

Page 17
Image 17
Burnham BV, BH manual Hot Water Performance Data -- High Motor Speed, Hot Water Performance Data -- Reduced Motor Speed