TABLE 9.5: PIPE AND CIRCULATOR SIZING FOR BOILER LOOP

 

 

 

 

 

 

(a)

 

(b)

 

 

(c)

 

 

 

(d)

 

 

(e)

 

 

 

BOILER

 

 

PIPE

 

 

 

TEMP

 

 

 

 

 

BOILER LOOP

 

 

 

 

 

 

FLOW

 

 

CIRCULATOR

MAX EQUIVA-

 

 

 

MODEL

 

 

SIZE

 

 

RISE

 

 

 

 

 

 

 

 

 

 

 

MODEL

 

LENT LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in NPT)

 

(GPM)

 

 

(F)

 

 

 

 

 

 

 

(ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FCM090

 

1

 

8.0

 

21

 

 

 

Taco 0014

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FCM090

 

1

 

8.0

 

21

 

 

Taco 0013 (Note #1)

 

230

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FCM120

 

1

 

8.0

 

29

 

 

 

Taco 0014

 

 

111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FCM120

 

1

 

9.0

 

25

 

 

 

Taco 0014

 

 

61

 

 

 

FCM120

 

1

 

12.0

 

19

 

 

Taco 0013 (Note #1)

 

28

 

 

 

 

NOTE: 1) Use isolation relay between Taco 0013 and FCM - see Figure 10.3

TABLE 9.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a)

 

(b)

(c)

 

 

 

 

(d)

 

 

(e)

 

(f)

BOILER

 

PIPE

 

 

 

MAX. I.W.H.

 

 

ALLIANCE™

 

 

 

I.W.H. LOOP MAX

 

 

FLOW

PRESSURE

 

 

CIRCULATOR

EQUIVALENT

MODEL

 

SIZE

 

 

INDIRECT WATER

 

 

 

 

DROP

 

LENGTH

 

 

 

 

 

 

 

 

 

 

 

HEATERS

 

MODEL

 

 

 

(in NPT)

 

(GPM)

(ft HEAD)

 

 

 

 

 

 

(ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL27SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL35SL

 

 

 

 

 

FCM090

 

1

 

 

8.0

 

3.0

 

 

 

AL50SL

(*)

 

Taco 0014

50

 

 

 

 

 

 

 

 

 

 

 

 

 

AL70SL

(*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL119SL (*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL27SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL35SL

 

Taco 0013

 

 

FCM090

 

1

 

 

8.0

 

3.0

 

 

 

AL50SL

(*)

 

190

 

 

 

 

 

 

 

 

(Note #3)

 

 

 

 

 

 

 

 

 

 

 

 

AL70SL

(*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL119SL (*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL27SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL35SL

 

 

 

 

 

FCM120

 

1

 

 

8.0

 

3.0

 

 

 

 

AL50SL

 

Taco 0014

71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL70SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL119SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL27SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL35SL

 

 

 

 

 

FCM120

 

1

 

 

8.0

 

5.0

 

 

 

 

AL50SL

 

Taco 0014

45

 

 

 

 

 

 

 

 

 

AL70SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL119SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note #2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL27SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL35SL

 

 

 

 

 

FCM120

 

1

 

 

8.0

 

5.0

 

 

 

 

AL50SL

 

Taco 0013

185

 

 

 

 

 

 

 

 

AL70SL

 

(Note #3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL119SL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note #2)

 

 

 

 

 

NOTES:

1)Indirect water heaters with an asterisk (*) will not achieve their catalog rating due to inadequate boiler output.

2)When used with an indirect heater having a pressure drop less than 3.0 ft of head, the Taco 0013 can be installed with up to 211 equivalent ft of 1” pipe.

3)Use isolation relay between Taco 0013 and FCM - see Figure 10.3

38