Operating Instructions and Parts Manual

Generator Operation (Continued)

INSTALLATION FOR STAND-BY USE

Precautions must be taken to prevent electrical back feeding into utility systems. This requires isolation of the electrical system. To isolate the electrical system, perform the following procedures:

1.Turn off the main electrical system switch prior to connecting the welder / generators.

2.In accordance with national and local standards, a double throw transfer switch must be installed in the system.

Always shut off main power prior to

temporary connection of the welder / generators to a building electrical system.

Installation of the welder / generator

as a backup electrical source must be performed by a qualified (licensed or certified) electrical technician.

Welder Operation

(FRONT PANEL SWITCH MUST BE SET TO WELDER POSITION)

WELDING LEAD ASSEMBLIES

Welding leads assemblies are not included with all units. Use copper welding cables in the size specified in Table 3.

GROUND CLAMP (SEE FIGURE 1)

1.Strip 1/2 inch of insulation from the end of one of the welding cables.

2.Loosen hex nuts on work clamp.

3.Insert the end of the welding cable through clamp handle and slide the bare wire under the clamp block.

4.Tighten the hex nuts, securing the cable in place.

ELECTRODE HOLDER (SEE FIGURE 2)

1.Strip 1/2 inch of insulation from the end of the other welding cable. Slide the bare wire into the wire sleeve.

2.Loosen the phillips head screw a few turns. Do not remove it completely. Pull the insulated

Figure 1

Wire

Handle

Sleeve

Welding

 

 

Cable

Cable Setscrew

Handle Phillips Head Screw

Electrode Holder

Figure 2

 

3.Loosen the set screw on the bottom of the electrode holder.

handle off of the electrode holder, and slide it over the welding cable.

4.Insert the welding cable / wire sleeve into the back of the brass body of the electrode holder.

 

 

 

TABLE 2 - EXTENSION CORDS

 

 

 

 

 

Maximum Recommended Lengths (in feet)

 

 

Amps

Watts 120 V

Watts 240 V

#8 Wire

#10 Wire

#12 Wire

#14 Wire

#16 Wire

2.5

300

600

 

1000

600

375

250

5

600

1200

 

500

300

200

125

7.5

900

1800

 

350

200

125

100

 

 

 

 

 

 

 

 

10

1200

2400

 

250

150

100

50

15

1800

3600

 

150

100

65

 

20

2400

4800

175

125

75

50

 

 

 

 

 

 

 

 

 

25

3000

6000

150

100

60

 

 

30

3600

7200

125

65

 

 

 

40

4800

9600

90

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 3 - WELDING CABLES

 

Total Cable Length *

0 - 20 feet (0 - 6 m)

20 - 40 feet (6 - 12 m)

40 - 60 feet (12 - 18 m)

Maximum Welding Current

 

Recommended Sizes of Copper Welding Cables

 

100 A

6 AWG (15 mm2)

6 AWG (15 mm2)

4 AWG (20 mm2)

150 A

6 AWG (15 mm2)

3 AWG (25 mm2)

2 AWG (35 mm2)

200 A

4 AWG (20 mm2)

2 AWG (35 mm2)

1 AWG (40 mm2)

250 A

3 AWG (25 mm2)

2 AWG (35 mm2)

1/0 AWG (55 mm2)

* Total cable length is the sum of the ground and electrode cable lengths.

 

 

 

 

 

www.chpower.com

 

 

 

8

Page 8
Image 8
Campbell Hausfeld GW4500 specifications Welder Operation