Installation
32 RTU Open

To wire a status switch to the controller

NOTES
Binary inputs 3, 5, 8, and 9 are configurable and may be used for Fan Status, Filter Status, Remote
Occupancy, or Door Contacts, if they have not already been used for their default functions.
Follow device manufacturer's installation and operating instructions.

Wiring a compressor safety

This is typically provided by the manufacturer with the rooftop equipment. A compressor safety status may be
monitored if available.

Wiring specifications

Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)