Carrier 25HCS3C warranty Physical Data, Vapor Line Sizing And Cooling Capacity Loss

Models: 25HCS3C

1 32
Download 32 pages 25.09 Kb
Page 3
Image 3
PHYSICAL DATA

PHYSICAL DATA

UNIT SIZE---SERIES, VOLTAGE

18---30

24---30

30---30

 

36---30

 

42---30

48---30

60---30

Operating Weight lb (kg)

207

204

211

 

252

 

239

314

361

(93.9)

(92.5)

(95.7)

 

(114.3)

 

(108.4)

(142.4)

(163.8)

 

 

 

Shipping Weight lb (kg)

218

236

222

 

287

 

250

348

395

(98.9)

(107.1)

(100.7)

 

(130.2)

 

(113.4)

(157.9)

(179.2)

 

 

 

Compressor Type

 

 

 

 

Scroll

 

 

 

 

REFRIGERANT

 

 

Freon (R--- 22)

 

 

 

Control

 

 

TXV (R--- 22 Hard Shutoff)

 

 

 

Charge lb (kg)

6.9

6.9

6.8

 

8.0

 

9.4

13.3

16.3

(3.0)

(3.0)

(3.1)

 

(3.6)

 

(4.3)

(6.0)

(7.4)

 

 

 

COND FAN

 

 

 

 

 

 

 

 

 

Air Discharge

 

 

 

 

Vertical

 

 

 

 

Air Qty (CFM)

2233

2614

3167

 

3334

 

3334

4046

4046

Motor HP

1/12

1/10

1/5

 

1/8

 

1/8

1/4

1/4

Motor RPM

800

800

800

 

800

 

800

800

800

COND COIL

 

 

 

 

 

 

 

 

 

Face Area (Sq ft)

19.4

21.56

19.40

 

25.15

 

17.60

25.15

30.18

Fins per In.

20

20

20

 

20

 

20

20

20

Rows

1

1

1

 

1

 

2

2

2

Circuits

5

6

6

 

6

 

8

8

11

VALVE CONNECT. (In.) ID

 

 

 

 

 

 

 

 

 

Vapor

5/8”

5/8”

3/4”

 

3/4”

 

7/8”

7/8”

7/8”

Liquid

 

 

 

 

3/8”

 

 

 

 

REFRIGERANT TUBES* (in.)OD

 

 

 

 

 

 

 

 

 

Vapor (0--- 80 Ft Tube Length)

5/8”

5/8”

3/4”

 

3/4”

 

7/8”

7/8”

1--- 1/8

Liquid (0--- 80 Ft Tube Length)

 

 

 

 

3/8”

 

 

 

 

*For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline. Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

LONG LINE APPLICATION: An application is considered ”Long

when outdoor unit is above indoor unit, and 60 ft. (18.28 m) when

line” when the total equivalent tubing length exceeds 80 ft. (24.38

the outdoor unit is below the indoor unit. Refer to Accessory

m) or when there is more than 20 ft. (6.09 m) vertical separation

Usage Guideline below for required accessories. See Longline

between indoor and outdoor units. These applications require

Application Guideline for required piping and system

additional accessories and system modifications for reliable system

modifications. Also, refer to the table below for vapor tube

operation. The maximum allowable total equivalent length is 250

diameters based on the total length to minimize the cooling

ft. (76.2 m). The maximum vertical separation is 200 ft. (60.96 m)

capacity loss.

 

 

 

 

 

 

 

Cooling Capacity Loss (%)

 

 

 

 

Maximum

Vapor Line

 

 

 

Total Equivalent Line Length ft. (m)

 

 

 

Unit Nominal

Liquid Line

Standard

 

 

Long Line Application Requires Accessories

 

Diameters

 

 

 

Size (Btuh)

Diameters

Application

 

 

 

(In.) OD

 

 

 

 

 

 

 

 

 

(In. OD)

 

 

 

 

 

 

 

 

 

 

 

26---50

51---80

81---100

101---125 126---150 151---175

176---200

201---225

226---250

 

 

 

 

 

 

 

 

(7.9---15.2)

(15.5---24.4)

(24.7---30.5)

(30.8---38.1)

(38.4---45.7) (46.0---53.3)

(53.6---61.0)

(61.3---68.6)

(68.9---76.2)

18,000

 

5/8

0

1

1

 

2

3

3

4

5

5

R---22 HP

 

3/4

0

0

0

 

0

1

1

1

1

2

24,000

 

5/8

0

1

3

 

3

5

6

7

8

9

 

3/4

0

0

0

 

1

1

1

2

2

3

R---22 HP

 

 

 

7/8

0

0

0

 

0

0

0

0

1

1

 

 

 

30,000

 

5/8

1

3

5

 

6

8

10

11

13

15

 

3/4

0

1

1

 

2

3

3

4

5

5

R---22 HP

 

 

 

7/8

0

0

0

 

1

1

1

2

2

2

 

 

 

36,000

3/8

3/4

0

1

2

 

3

4

5

6

7

8

R---22 HP

 

7/8

0

0

1

 

1

2

2

3

3

4

42,000

 

3/4

1

2

3

 

4

5

7

8

9

10

R---22 HP

 

7/8

0

1

1

 

2

2

3

4

4

5

48,000

 

3/4

1

2

4

 

5

7

8

10

11

13

 

7/8

0

1

2

 

2

3

4

5

5

6

R---22 HP

 

 

 

1---1/8

0

0

0

 

0

0

1

1

1

1

 

 

 

60,000

 

7/8

1

2

3

 

4

5

7

8

9

10

R---22 HP

 

1---1/8

0

0

1

 

1

1

2

2

2

3

Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica- tion Guidelines

25HCS3C

3

Page 3
Image 3
Carrier 25HCS3C warranty Physical Data, Vapor Line Sizing And Cooling Capacity Loss