Carrier 25HCS3C warranty Electrical Data, A-WEIGHTEDSOUND LEVEL dBA

Models: 25HCS3C

1 32
Download 32 pages 25.09 Kb
Page 7
Image 7
ELECTRICAL DATA

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

UNIT SIZE

V/PH

OPER VOLTS*

COMPR

FAN

MCA

WIRE

WIRE

LENGTH

LENGTH

FUSE**

 

 

 

 

 

SIZE†

SIZE†

ft.(m)‡

ft.(m)‡

or BRK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPS

 

 

MAX

MIN

LRA

RLA

FLA

 

60˚ C

75˚ C

60˚ C

75˚ C

18

 

 

 

41

9.8

0.5

12.7

14

14

124

118

20

 

 

 

(37.80)

(35.97)

 

 

 

 

 

 

 

 

 

 

 

24

 

 

 

54

15.13

0.7

19.6

14

14

80

76

30

 

 

 

(23.16)

(23.16)

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

72.5

13.50

1.2

18.6

14

14

85

81

30

 

 

 

(25.91)

(24.69)

 

 

 

 

 

 

 

 

 

 

 

36

208/230/1---60

253

197

88

18.68

0.9

24.2

12

12

103

98

40

(31.39)

(29.87)

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

104

17.90

0.9

24.0

12

12

104

99

40

 

 

 

(31.70)

(30.18)

 

 

 

 

 

 

 

 

 

 

 

48

 

 

 

137

22.22

1.2

29.0

10

10

138

131

50

 

 

 

(42.06)

(39.93)

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

148

28.85

1.2

37.3

8

8

167

159

60

 

 

 

(50.90)

(48.46)

 

 

 

 

 

 

 

 

 

 

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily

 

 

 

 

 

 

{If wire is applied at ambient greater than 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),

trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

A-WEIGHTED SOUND LEVEL (dBA)

 

STANDARD

TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment)

UNIT SIZE

RATING

 

 

 

 

 

 

 

125

250

500

1000

2000

4000

8000

 

(dB)

18

71

55

58

64.5

65

64.5

63

55.5

24

74

57.0

62.5

68.5

69.5

67.5

63.0

55.0

30

73

58.0

66.0

66.0

67.5

64.5

61.0

54.5

36

74

53.5

65.5

64.5

68.5

66.0

62.0

54.5

42

74

59.0

62.0

66.0

69.0

65.0

60.0

51.5

48

75

54.5

61.0

66.0

71.0

65.5

62.0

56.5

60

75

56.5

66.5

67.5

69.5

67.5

63.5

56.5

NOTE: Tested in accordance with ARI Standard 270---95. (Not listed with ARI).

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING _F (_C)

Heating Piston Size

18

10 (5.6)

42

24

10 (5.6)

52

30

10 (5.6)

57

36

10 (5.6)

57

42

10 (5.6)

67

48

9

(5.0)

67

60

10 (5.6)

78

25HCS3C

7

Page 7
Image 7
Carrier 25HCS3C warranty Electrical Data, A-WEIGHTEDSOUND LEVEL dBA, Charging Subcooling Txv-Typeexpansion Device