30RB060-390 Minimum Load Control Accessory
Installation Instructions
Part No: 00EFN900000100A
SAFETY CONSIDERATIONS
Installing, starting up, and servicing
Only trained, qualified installers and service technicians should install, start up, and service this equipment.
When working on
Follow all safety codes. Wear safety glasses and work gloves. Use care in handling equipment.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon- nect locations to alert others not to restore power until work is completed.
GENERAL
IMPORTANT: This accessory can only be used on units configured for Cooler Fluid Type (Configuration →SERV→FLUD = 1 [Water]). The minimum load control accessory (HGBP) is not allowed on units configured for Cooler Fluid Type (Configuration →SERV→FLUD = 2 [Brine]).
This control accessory reduces 30RB chiller capacities be- low the standard lowest capacity step. This capacity reduction provides more precise control of leaving fluid temperature during light load conditions.
The solenoid valve limits the amount of gas that can be bypassed from the condenser without impacting oil return.
One accessory package is required for
Table 1 — Modular Unit Combinations
UNIT SIZE | MODULE A | MODULE B |
30RBA315 | 30RBA160 | 30RBA160 |
30RBA330 | 30RBA170 | 30RBA160 |
30RBA345 | 30RBA170 | 30RBA170 |
30RBA360 | 30RBA190 | 30RBA170 |
30RBA390 | 30RBA190 | 30RBA190 |
NOTE: An “A” in the model number indicates the design series.
INSTALLATION
Examine the package contents for correct part numbers. If any of the components are damaged, file a claim with the shipping company and notify a Carrier representative.
See Table 2 for package contents. See Fig. 1 for dimensional drawings of tubes included in the kit.
The following material is field supplied:
•1/2 in. OD copper tubing
•standard 1/2 in. copper tube elbows and couplings as required
Install the Solenoid Valve
WARNING
Shut off all power to the unit. Lock out and
1.Shut off power to the unit.
2.Remove refrigerant charge from the unit.
3.Locate the
4.Remove the 1/2 in. NPT pipe plugs from the blank end of the cooler. Use an appropriate thread sealing compound and install one 1 in. — 14
5.Assemble the hot gas bypass line in the following order:
a.Remove the discharge stub tube and braze the cor- rect beaded tube in place.
b.Braze the ball valve to the beaded tube.
c.Braze the solenoid valve into the line.
d.Using
e.Clamp the
Use
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.