INSTALL FILTER DRIER(S) AND MOISTURE INDICA- TOR(S) Ð Every unit should have a ®lter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 ®lter driers and sight glasses. One ®lter drier and sight glass may be installed at A locations in Fig. 4. Or, 2 ®lter driers and sight glasses may be installed at B locations.
Select the ®lter drier for maximum unit capacity and mini- mum pressure drop. Complete the refrigerant piping from indoor unit to outdoor unit before opening the liquid and suc- tion lines at the outdoor unit.
TXV Ð Thermal Expansion Valve
Fig. 4 Ð Location of Sight Glass(es)
and Filter Drier(s)
INSTALL LIQUID LINE SOLENOID VALVE Ð SOLE- NOID DROP Ð It is recommended that a solenoid valve be placed in the main liquid line (see Fig. 4) between condens- ing unit (38AE/AKS) and fan coil (40RR, 40RE). (A liquid line solenoid valve is required when the liquid line length exceeds 100 ft [30.5 m] or when the condensing unit is con- nected to the chiller barrel in a
INSTALL LIQUID LINE SOLENOID VALVE (OPTIONAL)
ÐCAPACITY CONTROL Ð If
MAKE PIPING CONNECTIONS Ð Do not remove run- around loop from suction and liquid line stubs in the com- pressor compartment until piping connections are ready to be made. Pass nitrogen or other inert gas through piping while brazing to prevent formation of copper oxide.
Install
PROVIDE SAFETY RELIEF Ð A fusible plug is located on the compressor crankcase or in the liquid line (Fig. 5). Do not cap this plug. If local code requires additional safety devices, install them as directed.
NOTE: 38AKS024 has a fusible plug in the liquid line.
Fig. 5 Ð Location of Fusible Plug (38AE)
Step 4 Ð Install Accessories Ð Field install ac- cessories such as winter start control or
Step 5 Ð Complete Electrical Connections
POWER WIRING Ð Unit is factory wired for voltage shown on nameplate. Provide adequate fused disconnect switch within sight from unit and readily accessible from unit, but out of the reach of children. Lock switch open (off) to prevent power from being turned on while unit is being serviced. Discon- nect switch, fuses, and ®eld wiring must comply with na- tional and local code requirements. See Tables 5A and 5B.
Route power wires through opening in unit end panel to connection in unit control box as shown on unit label dia- gram and in Fig. 6. Unit must be grounded.
Affix crankcase heater warning sticker to unit disconnect switch.
CONTROL CIRCUIT WIRING Ð Control voltage is 24 v. See Fig. 7 and unit label diagram for
| LEGEND |
EQUIP GND Ð Equipment Ground | |
NEC | Ð National Electrical Code |
Factory Wiring
Field Wiring
Fig. 6 Ð Main Power Supply Wiring
7