Carrier 38AE014, 38AE012 Ð Remote Thermostat Wiring, A Ð Electrical Data 3 Ph/60 Hz, Llsv Ð

Models: 38AE014 38AE016 38AE012

1 20
Download 20 pages 7.37 Kb
Page 8
Image 8
LLSV Ð

 

 

LEGEND

 

C

Ð Compressor Contactor

R Ð Relay

HD

Ð Heating Device

Factory Wiring

IFC

Ð

Indoor-Fan Contactor

Field Wiring

LLSV Ð

Liquid Line Solenoid Valve

 

NOTES:

1. Combination LLSV plus IFC va should not exceed 30 va.

2. Do not exceed 5 va (24 vac) per coil.

3. If va values shown in Notes 1 and 2 must be exceeded, use accessory relay transformer package 38AE900001.

Fig. 7 Ð Remote Thermostat Wiring

Table 5A Ð Electrical Data (3 Ph/60 Hz)

 

 

 

 

 

UNIT

 

 

 

COMPR

FAN MOTORS (Single Phase)

UNIT

 

 

Volts

 

 

 

 

MOCP

 

 

Total

FLA (ea)

 

Model

 

 

Supplied*

MCA

ICF

RLA

LRA

Fan No.

kW

 

 

 

 

 

Nameplate

 

 

 

 

 

 

(Fuse)

 

 

Fans

 

 

 

 

 

 

Min

 

Max

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

501

208-230

 

187

 

253

62.5

178

100

43.6

170

 

4.3

3.7

 

38AE012

201

380

 

342

 

418

35.0

101

50

24.0

93

2

4.3

3.7

1.41

601

460

 

414

 

528

29.1

81

40

20.0

77

2.3

1.9

 

 

 

 

 

 

101

575

 

518

 

660

22.8

67

35

15.7

62

 

1.8

1.8

 

 

501

208-230

 

187

 

253

69.3

199

100

49.3

191

 

4.3

3.7

 

38AE014

201

380

 

342

 

418

38.0

112

60

26.5

104

2

4.3

3.7

1.41

601

460

 

414

 

528

31.7

84

50

22.1

80

2.3

1.9

 

 

 

 

 

 

101

575

 

518

 

660

25.6

73

40

17.9

69

 

1.8

1.8

 

 

501

208-230

 

187

 

253

87.5

274

125

63.6

266

 

4.3

3.7

 

38AE016

201

380

 

342

 

418

49.3

153

80

36.0

145

2

4.3

3.7

1.41

601

460

 

414

 

528

40.7

124

60

29.3

120

2.3

1.9

 

 

 

 

 

 

101

575

 

518

 

660

33.0

100

50

23.8

96

 

1.8

1.8

 

 

501

208-230

 

187

 

254

93.4

353

150

67.9

345

 

4.3

3.7

 

38AKS024

201

380

 

342

 

418

49.7

199

80

34.6

191

2

4.3

3.7

1.41

601

460

 

414

 

508

48.1

177

80

34.7

173

2.3

1.9

 

 

 

 

 

 

101

575

 

518

 

632

40.1

124

60

28.8

120

 

1.8

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5B Ð Electrical Data (3 Ph/50 Hz)

 

 

 

 

 

UNIT

 

 

 

COMPR

FAN MOTORS 230 v (Single Phase)

UNIT

 

 

Volts

 

 

 

 

MOCP

 

 

Total

 

FLA (ea)

 

Model

 

 

Supplied*

MCA

ICF

RLA

LRA

 

Fan No.

kW

 

 

 

 

 

 

Nameplate

 

 

 

 

 

 

(Fuse)

 

 

Fans

 

 

 

 

 

 

 

Min

 

Max

 

 

 

 

1

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38AE012

803

230

 

198

 

264

47.5

134

75

32.9

128

2

2.9

 

3.5

1.20

903

400

 

342

 

457

31.4

80

50

20.0

74

 

 

 

 

 

 

 

 

 

38AE014

803

230

 

198

 

264

51.0

149

75

35.7

143

2

2.9

 

3.5

1.20

903

400

 

342

 

457

34.0

89

50

22.1

83

 

 

 

 

 

 

 

 

 

38AE016

803

230

 

198

 

264

66.9

206

100

47.9

200

2

2.9

 

3.5

1.20

903

400

 

342

 

457

43.0

121

60

29.3

115

 

 

 

 

 

 

 

 

 

38AKS024

803

230

 

198

 

254

91.8

213

150

67.9

207

 

 

 

 

 

303

346

 

311

 

380

51.5

121

80

33.3

115

2

2.9

 

3.5

1.20

 

903

400

 

342

 

440

50.2

179

80

34.6

173

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Ð Full Load Amps (Fan Motors)

ICF

Ð

Maximum Instantaneous Current Flow during start-up (LRA of compressor plus total FLA of fan motors)

kW

Ð

Total Fan Motor Input (kilowatts)

LRA

Ð

Locked Rotor Amps

MCA

Ð

Minimum Circuit Amps per NEC (U.S.A.), Section 430-24

MOCP Ð

Maximum Overcurrent Protection (amps)

RLA

Ð

Rated Load Amps (Compressor)

*Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits.

NOTES:

1.The MCA and MOCP values are calculated in accordance with the National Electrical Code (NEC) article 440 (U.S.A. standard).

2.Motor RLA and LRA values are established in accordance with Underwriters' Laboratories (UL) Standard 1995 (U.S.A. standard).

8

Page 8
Image 8
Carrier 38AE014 Ð Remote Thermostat Wiring, A Ð Electrical Data 3 Ph/60 Hz, B Ð Electrical Data 3 Ph/50 Hz, Llsv Ð