38CKBÐ50 Hz Air Conditioning Unit
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and national electric codes for special requirements.
Recognize safety information. This is the
Understand the signal word DANGER, WARNING, or CAU- TION. These words are used with the
Before installing, modifying, or servicing system, main elec- trical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
INSTALLATION
Step 1ÐCheck Equipment and Jobsite
UNPACK UNIT Ð Move to final location. Remove carton taking care not to damage unit.
INSPECT EQUIPMENT Ð File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating label on unit service panel. (See Fig. 2.) It contains information needed to properly install unit. Check rating label to be sure unit matches job specifications.
Step 2ÐInstall on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tiedown bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow
A94356
Fig. 1ÐModel 38CKB
For proper airflow, a
On rooftop applications, locate unit 6 in. (152mm) above roof surface. Where possible, place unit above a
Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Step 3ÐReplace Indoor AccuRater® Piston, if Required
Check indoor coil piston to see if it matches the required piston shown on unit rating label. If it does not match, replace indoor coil piston with piston shipped with this unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination.
Remove indoor coil piston if unit is to be installed on system with a TXV metering device.
Step 4ÐMake Piping Connections
Outdoor units may be connected to indoor sections using accessory tubing package or
NOTE: In some cases, noise in the living area has been traced to gas pulsations from improper installation of equipment.
INSTALLATION RECOMMENDATIONS
1.Locate the unit away from windows.
2.Ensure that vapor and liquid tube diameters are appropriate to the capacity of the unit. (See Table 1.)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.