CONNECT CONTROL WIRING Ð Route
Use furnace transformer,
NOTE: Use of available
Step 6ÐCompressor Crankcase Heat
When equipped with a crankcase heater, energize heater a mini- mum of 24 hrs before starting unit. To energize heater only, set thermostat to OFF position and close electrical disconnect to outdoor unit.
A crankcase heater is required if the refrigerant tubing is longer than 50 ft (15.24m).
Step 7ÐInstall Electrical Accessories, If Any
Refer to the individual instructions packaged with the kit or accessory when installing.
Step 8ÐStart-Up and Check Charge
To prevent compressor damage or personal injury, observe the following:
·Do not overcharge system with refrigerant.
·Do not operate unit in a vacuum or at negative pressure.
·Do not disable
In scroll compressor applications:
·Dome temperatures may be hot.
·In 3 phase application, incorrect phasing will cause reverse rotation, resulting in elevated noise levels, equalized pres- sures and reduced current draw. Correct by reversing power connection L1 and L2 on contactor.
To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
·Back seating service valves are not equipped with Schrader valves. Fully back seat (counter clockwise) valve stem before removing gage port cap.
·Front seating service valves are equipped with Schrader valves.
Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
1.Fully back seat (open) liquid and vapor tube service valves.
2.Unit is shipped with valve stem(s) front seated and caps installed. Replace stem caps after system is opened to refrig- erant flow (back seated). Replace caps
3.Close electrical disconnects to energize system.
4.Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5.Set room thermostat at COOL and fan switch at FAN or AUTO, as desired. Operate unit for 15 minutes. Check system refrigerant charge.
6.Factory charge is shown on unit rating label. Adjust charge by following procedure shown on charging tables located on unit.
Step 9ÐLeave User's Manual with Owner
For continued high performance and to minimize possible equip- ment failure, periodic maintenance MUST be performed on this equipment.
Leave User's Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual. Frequency of maintenance may vary depending on geographic areas, such as coastal applications which require more frequent maintenance.