Carrier 38HDR018-060 specifications A - 38HDF018-036Physical Data

Models: 38HDR018-060 38HDF018-036

1 16
Download 16 pages 23.67 Kb
Page 4
Image 4
Table 1A — 38HDF018-036 Physical Data

Only use factory specified liquid-line filter driers with rated working pressures less than 600 psig.

NOTE: Do not install a suction-line filter drier in liquid line.

MAKE PIPING SWEAT CONNECTIONS — Remove plastic caps from liquid and suction service valves. Use refrigerant grade tubing. Service valves are closed from the factory and are ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using ei- ther silver bearing or non-silver bearing brazing material. Con- sult local code requirements. Refrigerant tubing and the indoor coil are now ready for leak testing.

NOTE: Unit is shipped with R-410A factory charge indicated on nameplate.

Pass nitrogen or other inert gas through piping while braz- ing to prevent formation of copper oxide.

To avoid damage while brazing, service valves should be wrapped with a heat-sinking material such as a wet cloth.

When brazing tubing sets to the service valves, a brazing shield MUST be used to prevent damage to the painted unit surface.

PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.

Table 1A — 38HDF018-036 Physical Data

 

UNIT 38HDF

018

 

024

 

030

 

036

NOMINAL CAPACITY (Tons)

1.5

 

2.0

 

2.50

 

3.0

OPERATING WEIGHT (lb)

166

 

176

 

187

 

250

REFRIGERANT TYPE

 

 

 

 

R-410A

 

METERING DEVICE

 

 

AccuRater (Located at Fan Coil)

 

CHARGE (lb)*

4.8

 

5.3

 

5.0

 

7.1

OUTDOOR FAN

 

 

 

 

 

 

 

Rpm/Cfm

840/1720

 

840/1720

 

840/1720

 

850/1720

 

 

 

Diameter (in.)

18

 

18

 

18

 

24

No. Blades

3

 

3

 

3

 

3

Motor (hp)

1/8

 

1/8

 

1/8

 

1/4

OUTDOOR COIL

 

 

 

 

 

 

 

Face Area (sq ft)

5.82

 

7.27

 

7.27

 

12.1

 

 

 

No. Rows

2

 

3

 

3

 

2

FPI

20

 

20

 

20

 

20

HIGH PRESSURE SWITCH

 

 

 

 

 

 

 

Cut-In (psig)

420 ± 25

 

420 ± 25

 

420 ± 25

 

420 ± 25

 

 

 

Cutout (psig)

650 ± 10

 

650 ± 10

 

650 ± 10

 

650 ± 10

LOW PRESSURE SWITCH

 

 

 

 

 

 

 

Cut-In (psig)

45 ± 25

 

45 ± 25

 

45 ± 25

 

45 ± 25

 

 

 

Cutout (psig)

20 ± 5

 

20 ± 5

 

20 ± 5

 

20 ± 5

REFRIGERANT LINES

 

 

 

 

 

 

 

Connection Type

 

 

 

 

Sweat

 

Liquid Line (in.) OD

3/

 

3/

 

3/

 

3/

 

 

 

Vapor Line (in.) OD

8

 

8

 

8

 

8

5/8

 

5/8

 

3/4

 

3/4

Max Length (ft)

200

 

200

 

200

 

200

Max Lift (ft)

65

 

65

 

65

 

65

Max Drop (ft)

150

 

150

 

150

 

150

COMPRESSOR

 

 

 

 

 

 

 

Type

 

 

 

 

Scroll

 

Model

ZP16K5E-PFV

 

ZP21K5E-PFV

 

ZP25K5E-PFV

 

ZP34K5P-PFV

 

 

 

Oil Charge (POE - oz)

25.0

 

25.0

 

25.0

 

42.0

Accumulator

 

 

 

 

Yes

 

 

CONTROLS

 

 

 

 

 

 

 

Fusible Plug (F)

 

 

 

210

 

 

Control Voltage†

 

 

 

 

24 vac

208/230 v, Single and 3 Phase,

System Voltage

208/230 v

 

208/230 v

 

208/230 v

 

 

 

 

460 v, 3 Phase

 

 

 

 

 

 

 

 

FINISH

 

 

 

 

Gray

 

 

LEGEND

 

 

*Unit shipped with full factory charge. See ARI (Air Conditioning and

FPI

Fins Per Inch

 

 

Refrigeration Institute) capacity table for proper charge and piston

 

 

for each fan coil type.

 

POE

Polyol Ester

 

 

 

 

 

†24 v and a minimum of 40 va is provided in the fan coil unit.

 

 

 

 

4

Page 4
Image 4
Carrier 38HDR018-060 specifications A - 38HDF018-036Physical Data