Only use factory specified
NOTE: Do not install a
MAKE PIPING SWEAT CONNECTIONS — Remove plastic caps from liquid and suction service valves. Use refrigerant grade tubing. Service valves are closed from the factory and are ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using ei- ther silver bearing or
NOTE: Unit is shipped with
Pass nitrogen or other inert gas through piping while braz- ing to prevent formation of copper oxide.
To avoid damage while brazing, service valves should be wrapped with a
When brazing tubing sets to the service valves, a brazing shield MUST be used to prevent damage to the painted unit surface.
PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.
Table 1A — 38HDF018-036 Physical Data
| UNIT 38HDF | 018 |
| 024 |
| 030 |
| 036 |
NOMINAL CAPACITY (Tons) | 1.5 |
| 2.0 |
| 2.50 |
| 3.0 | |
OPERATING WEIGHT (lb) | 166 |
| 176 |
| 187 |
| 250 | |
REFRIGERANT TYPE |
|
|
|
|
| |||
METERING DEVICE |
|
| AccuRater (Located at Fan Coil) |
| ||||
CHARGE (lb)* | 4.8 |
| 5.3 |
| 5.0 |
| 7.1 | |
OUTDOOR FAN |
|
|
|
|
|
|
| |
Rpm/Cfm | 840/1720 |
| 840/1720 |
| 840/1720 |
| 850/1720 | |
|
|
| ||||||
Diameter (in.) | 18 |
| 18 |
| 18 |
| 24 | |
No. Blades | 3 |
| 3 |
| 3 |
| 3 | |
Motor (hp) | 1/8 |
| 1/8 |
| 1/8 |
| 1/4 | |
OUTDOOR COIL |
|
|
|
|
|
|
| |
Face Area (sq ft) | 5.82 |
| 7.27 |
| 7.27 |
| 12.1 | |
|
|
| ||||||
No. Rows | 2 |
| 3 |
| 3 |
| 2 | |
FPI | 20 |
| 20 |
| 20 |
| 20 | |
HIGH PRESSURE SWITCH |
|
|
|
|
|
|
| |
420 ± 25 |
| 420 ± 25 |
| 420 ± 25 |
| 420 ± 25 | ||
|
|
| ||||||
Cutout (psig) | 650 ± 10 |
| 650 ± 10 |
| 650 ± 10 |
| 650 ± 10 | |
LOW PRESSURE SWITCH |
|
|
|
|
|
|
| |
45 ± 25 |
| 45 ± 25 |
| 45 ± 25 |
| 45 ± 25 | ||
|
|
| ||||||
Cutout (psig) | 20 ± 5 |
| 20 ± 5 |
| 20 ± 5 |
| 20 ± 5 | |
REFRIGERANT LINES |
|
|
|
|
|
|
| |
Connection Type |
|
|
|
| Sweat |
| ||
Liquid Line (in.) OD | 3/ |
| 3/ |
| 3/ |
| 3/ | |
|
|
| ||||||
Vapor Line (in.) OD | 8 |
| 8 |
| 8 |
| 8 | |
5/8 |
| 5/8 |
| 3/4 |
| 3/4 | ||
Max Length (ft) | 200 |
| 200 |
| 200 |
| 200 | |
Max Lift (ft) | 65 |
| 65 |
| 65 |
| 65 | |
Max Drop (ft) | 150 |
| 150 |
| 150 |
| 150 | |
COMPRESSOR |
|
|
|
|
|
|
| |
Type |
|
|
|
| Scroll |
| ||
Model |
|
|
| |||||
|
|
| ||||||
Oil Charge (POE - oz) | 25.0 |
| 25.0 |
| 25.0 |
| 42.0 | |
Accumulator |
|
|
|
| Yes |
|
| |
CONTROLS |
|
|
|
|
|
|
| |
Fusible Plug (F) |
|
|
| 210 |
|
| ||
Control Voltage† |
|
|
|
| 24 vac | 208/230 v, Single and 3 Phase, | ||
System Voltage | 208/230 v |
| 208/230 v |
| 208/230 v |
| ||
|
|
| 460 v, 3 Phase | |||||
|
|
|
|
|
|
|
| |
FINISH |
|
|
|
| Gray |
| ||
| LEGEND |
|
| *Unit shipped with full factory charge. See ARI (Air Conditioning and | ||||
FPI | — Fins Per Inch |
|
| Refrigeration Institute) capacity table for proper charge and piston | ||||
|
| for each fan coil type. |
| |||||
POE | — Polyol Ester |
|
|
| ||||
|
| †24 v and a minimum of 40 va is provided in the fan coil unit. | ||||||
|
|
|
|