Carrier 38AYB ÐRefrigerant Tube Dimensions/Connections, ÐLiquid Service Valve Mechanical Fitting

Models: 38AYB 38BYB 38YCB(P)

1 4
Download 4 pages 52.13 Kb
Page 2
Image 2
Fig. 2ÐRefrigerant Tube Dimensions/Connections

AIR DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIELD POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY CONN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

78DIA HOLE WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 18DIA KNOCKOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND 1 38DIA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KNOCKOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIELD CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY CONN

SUCTION LINE CONN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

78DIA HOLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE CONN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A93578

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

 

 

 

LIQUID TUBE

VAPOR TUBE

 

Conn Dia

 

 

 

 

Tube Dia

Conn Dia

Tube Dia

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018, 024

 

 

3/8

 

 

 

 

3/8

 

5/8

5/8

 

030, 036

 

 

3/8

 

 

 

 

3/8

 

3/4

3/4

 

042, 048

 

 

3/8

 

 

 

 

3/8

 

7/8

7/8

 

060

 

 

3/8

 

 

 

 

3/8

 

7/8

1-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult your local distributor.

Fig. 2ÐRefrigerant Tube Dimensions/Connections

PISTON BODY Fig. 3ÐLiquid Service Valve Mechanical Fitting

PISTON

PISTON RETAINER

Assembly (38YCP Model) LIQUID SERVICE

VALVE ADAPTER

Fig. 4ÐSuction Service Valve with MechanicalFERRULE

Adapter (38YCP Model)LOCK NUT

A94030

Fig. 3ÐLiquid Service Valve Mechanical Fitting

Assembly (38YCP Model)

NOTE: A backup wrench on the hex part of the suction valve fitting is required while tightening.

The tube end must stay bottomed in the service valve during final assembly to ensure proper seating, sealing, and rigidity.

MECHANICAL FITTING REPAIR

To replace damaged ferrule or tubing, proceed as follows.

1.Attach gages to service valves.

2.Close liquid service valve and operate unit in cooling mode to pump refrigerant charge into condenser coil.

3.When suction pressure reaches 5 psig, shut unit off. Do not operate unit in a vacuum.

VALVE FITTING

FERRULE

LOCK NUT

A92120

Fig. 4ÐSuction Service Valve with Mechanical

Adapter (38YCP Model)

 

 

 

FERRULE

 

 

 

LOCK NUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUBING Fig. 5ÐLock Nut/Ferrule Positioning

A92121

Fig. 5ÐLock Nut/Ferrule Positioning

4.Close suction service valve and recover refrigerant in tubing.

5.Back-off locknut and ferrule onto tube.

6.Remove damaged part of tubing using tubing cutter. Repeat installation procedure previously outlined using new ferrule.

7.Evacuate tubing set and indoor coil. Check for leaks.

8.Open service valves or recharge unit. Check refrigerant charge.

LOCK NUT

TUBING

MARK ON LOCK NUT

AND TUBE

A92122

Fig. 6ÐProper Marking of Valve Assembly

2

Page 2
Image 2
Carrier 38AYB ÐRefrigerant Tube Dimensions/Connections, ÐLiquid Service Valve Mechanical Fitting, Assembly 38YCP Model